Manual Mode
Manual mode level 3
LED on Man. button lights up permanently in red
Briefly press button 1/9 to trigger a broadcast command. Whether the command that is sent
first is an on or off command depends on the status of group 1. Each further keypress toggles
all lights via broadcast. The LED on button 1/9 shows the switch status. All lights react to a
broadcast command even if group assignment has not yet taken place.
A long keypress on button 5/13 triggers a quick exchange command. This function makes it
possible to replace a faulty ECG even without the ETS (see chapter 11.5 ECG easy replacement).
A long keypress on button 6/14 activates the converter inhibit mode. If the power supply for the
connected emergency lights is turned off within 15 minutes after activating the converter inhibit
mode, the lights are turned off instead of changing into emergency mode. This operating mode
may be necessary during the commissioning and installation process to prevent constant
emergency lighting and battery discharge.
If the gateway detects a fault, the LEDs on buttons 2/10 to 4/12 and 7/15 to 8/16 show the
exact type of fault. The LED is constantly lit up in red. The faults are as follows:
LED Button 2/10  Converter fault
LED Button 3/11  ECG fault
LED Button 4/12  Lamp fault
LED Button 7/15  DALI short-circuit
LED Button 8/16  KNX fault
5.2

2 channel device

The DALI gateway S128 KNX has 9 operating buttons and LEDs on the front side, which offer
numerous possibilities for manual control and broadcast and analysis functions.
The buttons and LEDs are accessible without having to remove the cover. During KNX bus
operation and in the absence of any errors, all 9 LEDs are switched off. If the gateway detects
an error (e.g. a faulty lamp or KNX failure), only the LED on the Man. button lights up in red and
flashes quickly. During programming (e.g. during installation) all LEDs light up in red and flash
slowly.
Activate the manual mode with a long keypress on the button in the bottom right-hand
corner.
The manual mode ends automatically 60 seconds after the last time the button has been
activated.
Manual DALI gateway S64 KNX/S128 KNX