B.7 H Parameters: Multi-Function Terminals
u

H3: Multi-Function Analog Inputs

No.
(Addr.
Name
Hex)
H3-01
Terminal A1 Signal
(0410)
Level Selection
H3-02
Terminal A1 Function
(0434)
Selection
H3-03
Terminal A1 Gain
(0411)
Setting
H3-04
Terminal A1 Bias
(0412)
Setting
H3-05
Terminal A3 Signal
(0413)
Level Selection
H3-06
Terminal A3 Function
(0414)
Selection
H3-07
Terminal A3 Gain
(0415)
Setting
H3-08
Terminal A3 Bias
(0416)
Setting
H3-09
Terminal A2 Signal
(0417)
Level Selection
H3-10
Terminal A2 Function
(0418)
Selection
H3-11
Terminal A2 Gain
(0419)
Setting
H3-12
(041A) Terminal A2 Bias
Setting
H3-13
Analog Input Filter
(041B)
Time Constant
H3-14
Analog Input Terminal
(041C)
Enable Selection
H3-16
Terminal A1 Offset
(02F0)
284
LCD Display
0: 0 to 10 V
Term A1 Level
1: -10 to 10 V
0: 0-10V,
2: 4 to 20 mA
(LowLim=0)
3: 0 to 20 mA
1: 0-10V, (BipolRef)
2: 4-20 mA
Note:
3: 0-20 mA
Sets the function of terminal A1.
Term A1 FuncSel
Sets the level of the input value selected in H3-02 when 10 V is
input at terminal A1.
Terminal A1 Gain
Sets the level of the input value selected in H3-02 when 0 V is
input at terminal A1.
Terminal A1 Bias
0: 0 to 10 V
Term A3 Level
1: -10 to 10 V
0: 0-10V,
2: 4 to 20 mA
(LowLim=0)
3: 0 to 20 mA
1: 0-10V, (BipolRef)
2: 4-20 mA
Note:
3: 0-20 mA
Sets the function of terminal A3.
Term A3 FuncSel
Sets the level of the input value selected in H3-06 when 10 V is
input at terminal A3.
Terminal A3 Gain
Sets the level of the input value selected in H3-06 when 0 V is
input at terminal A3.
Terminal A3 Bias
0: 0 to 10 V
Term A2 Level
1: -10 to 10 V
0: 0-10V,
2: 4 to 20 mA
(LowLim=0)
3: 0 to 20 mA
1: 0-10V, (BipolRef)
2: 4-20 mA
Note:
3: 0-20 mA
Sets the function of terminal A2.
Term A2 FuncSel
Sets the level of the input value selected in H3-10 when 10 V
(20 mA) is input at terminal A2.
Terminal A2 Gain
Sets the level of the input value selected in H3-10 when 0 V (0
or 4 mA) is input at terminal A2.
Terminal A2 Bias
Sets a primary delay filter time constant for terminals A1, A2,
A1/A2 Filter T
and A3. Used for noise filtering.
Determines which analog input terminals will be enabled when
A1/A2 Sel
a digital input programmed for "Analog input enable"
1: A1 Available
(H1-oo = C) is activated.
2: A2 Available
1: Terminal A1 only
3: A1/A2 Available
2: Terminal A2 only
4: A3 Available
3: Terminals A1 and A2 only
5: A1/A3 Available
4: Terminal A3 only
6: A2/A3 Available
5: Terminals A1 and A3
7: All Available
6: Terminals A2 and A3
7: All terminals enabled
Term A1 Offset
Adds an offset when the analog signal to terminal A1 is at 0 V.
Description
Use Jumper S1 to set input terminal A1 for a
current or voltage input signal.
Use Jumper S1 to set input terminal A3 for a
current or voltage input signal.
Use Jumper S1 to set input terminal A2 for a
current or voltage input signal.
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
Values
Page
Default: 0
160
Range: 0 to 3
Default: 0
160
Range: 0 to 32
Default: 100.0%
Min.: -999.9
160
Max.: 999.9
Default: 0.0%
Min.: -999.9
160
Max.: 999.9
Default: 0
161
Range: 0 to 3
Default: 20
161
Range: 0 to 32
Default: 100.0%
Min.: -999.9
162
Max.: 999.9
Default: 0.0%
Min.: -999.9
162
Max.: 999.9
Default: 2
162
Range: 0 to 3
Default: B
162
Range: 0 to 32
Default: 100.0%
Min.: -999.9
162
Max.: 999.9
Default: 0.0%
Min.: -999.9
162
Max.: 999.9
Default: 0.03 s
Min.: 0.00
Max.: 2.00
Default: 7
Range: 1 to 7
Default: 0
Min.: -500
Max.: 500