Also ensure that all door fastening lugs properly hook into the base frame.
①
4.8
Requirements for the electrical connection
The Wallbox is approved for fixed installation only. The national regulations and standards
must be followed during installation of the supply line.
An RCBO circuit breaker is already integrated in the column.
Also note the regulations in place for upstream protection from transient overvoltages (e.g.
through lightning), for example, by using SPDs (Surge Protection Device) according to IEC
60364-7-722.
VersiCharge Column Mounting
Hardware Installation Manual, 06/2022, A5E51460654-AB
Side panel lock with key for security purposes
Mounting / Installing / Connecting
4.8 Requirements for the electrical connection
35