Switching On And Testing - Siemens VersiCharge 8EM1390 A0 Series Installation Instructions Manual

Mounting on column
Table of Contents

Advertisement

Mounting / Installing / Connecting

4.9 Switching on and testing

4.9
Switching on and testing
Procedure for switching on and checking the Wallbox
Perform the following steps to switch on and check the charging unit.
1. Switch on the power supply of the Wallbox supply line.
2. Switch on the back-up fuses, the switch disconnector and the RCCB.
3. The "Power" LED lights up on the Wallbox.
If the display does not light up on the Wallbox, check the power supply using a measuring
instrument. When measuring, follow the regional regulations.
4. Configure the Wallbox according to the operating instructions:
– German (https://support.industry.siemens.com/cs/at/de/view/109782228)
– English (https://support.industry.siemens.com/cs/at/en/view/109782228)
Test run with acceptance
• Perform the measurements according to DGUV regulation 3 or the comparable regional
regulations.
NOTICE
Danger for devices from high voltage
When conducting insulation resistance measurements between active conductors or
between active conductors and protective conductor, the measurement direct voltage
should be limited to 250 V. Otherwise, the device can be destroyed.
Final work
1. Remove the packing material and protective films.
2. Clean the unit if required.
3. Complete the commissioning report in accordance with the regional regulations, e.g.
DGUV regulation 3.
NOTE
The Wallboxes are designed for continuous operation. Daily restarts (Power Cycle) can affect
the service life of the components.
36
VersiCharge Column Mounting
Hardware Installation Manual, 06/2022, A5E51460654-AB