Diagrams/Circuitry; List Of Diagrams/Circuitry - Siemens VersiCharge 8EM1390 A0 Series Installation Instructions Manual

Mounting on column
Table of Contents

Advertisement

Diagrams/Circuitry

8.1

List of diagrams/circuitry

The following is an overview of all diagrams. Take note of the special information provided.
NOTE
The selection of the supply line has to be made differently
If applicable, the following regulations must be observed:
• DIN VDE 0100-722 (Power supply for electric vehicles)
• IEC 60364-5-53 (Selection and erection of electrical equipment - Devices for protection for
safety, isolation, switching, control and monitoring)
• VDE‐AR‐N‐4100 (Technical rules for the connection and operation of customer installa­
tions to the low voltage network)
• DIN VDE 0298-4 (Application of cables and cords in power installations)
TN-C Un 230V
Figure 8-1  Terminal box 1x7.4 kW 1-phase
VersiCharge Column Mounting
Hardware Installation Manual, 06/2022, A5E51460654-AB
Trenner
Disconnector 40A
5TL1240-0
2
Cu 3x25
Wallbox
Up to 5x35
7,4kW
1~
FI/LS
RCBO 40A, 30mA
5SU1324 -7FA40
10kA
Cu 3x6
Überspannungsableiter
Surge Protec on device
Cat 1, 2, 3
DVA EMOB 3P 255 FM
Meldekontakt
Poten al free
Signal contact
8
43

Advertisement

Table of Contents
loading

Table of Contents