Assembly Procedure - Siemens VersiCharge 8EM1390 A0 Series Installation Instructions Manual

Mounting on column
Table of Contents

Advertisement

Mounting / Installing / Connecting

4.2 Assembly procedure

4.2
Assembly procedure
Specific safety measures
Risk of electric shock when moist due to condensed water
Before commissioning the Wallbox, an authorized and qualified electrician must check
whether there is moisture in the Wallbox. Remove even small amounts of condensed water
before commissioning. Take appropriate measures for drying.
Do not switch off the power supply for an extended period of time after commissioning. This
prevents condensation in the Wallbox. If the Wallbox is to be switched off for a longer period
of time, you need to provide suitable moisture protection.
Risk of accident
Risk of accident through a non-secured Wallbox.
• Do not put the Wallbox down unattended.
• Place or lay down the Wallbox and its parts in such a way that the Wallbox and its parts
Risk of accident
Risk of accident in limited space. Leave sufficient clearance to surrounding obstacles to avoid
collisions and crushing when setting up the Wallbox.
• Ensure that there is sufficient clearance to the surrounding obstacles when setting the
• Keep the working area free of objects to avoid the risk of tripping.
20
DANGER
WARNING
cannot tip over or fall down.
WARNING
load down.
VersiCharge Column Mounting
Hardware Installation Manual, 06/2022, A5E51460654-AB