Appendix C: FACP with Keltron

The following figure illustrates the connections between the FACP and Keltron Receiver/Transmit-
ter.
P
CAUTION:
!
FOR REASONS OF WIRING DIAGRAM CLARITY, TERMINAL DESIGNATIONS OF KELTRON
MODULES ARE NOT SHOWN IN ACTUAL ORDER. FOLLOW KELTRON MANUAL AND
MODULE MARKINGS FOR EXACT TERMINAL LOCATIONS TO PREVENT SEVERE MODULE
DAMAGE!
IMPORTANT! All connections between the FACP and Keltron modules must be made within 20
feet and enclosed within conduit or equivalently protected against mechanical injury.
Keltron 95M3158 TTM-RPS
1.
Terminals 7 and 8: Remote station alarm/trouble inputs.
2.
Terminals 9 and 10: Sprinkler supervisory input.
152
POSSIBLE EQUIPMENT DAMAGE
UL-Listed
Sprinkler Supervisory Signal
Note: Cut TBL jumper on 4XTMF module to send
alarm/trouble signal from the same pair or terminals.
Fire Alarm Control Panel
(terminal blocks are not shown in their
actual positions in order to clarify wiring
connections)
Figure C.1 Keltron Wiring
MS-5UD & MS-10UD Series Manual — P/N 52626:C2 1/24/2012
UL-Listed
Alarm/Trouble Signal
4XTMF Module
*Note: For more
information, refer to the
Keltron manual.