Master Programming Level

View Events

HISTORY
1=VIEW EVENTS

2=ERASE HISTORY

History Screen
While displaying the View Events screen, press 1 to view all events, 2 to view only alarms or 3 to view other events. Use the up and
down arrow keys to scroll through all of the displayed events.
Erase History
The Erase History option allows a user to erase all events from the history file. This will provide a clean slate in order to use the history
file to track future events. Pressing 2 while viewing the History Screen will display the following screen:
Pressing 1 while viewing the Erase History Screen will erase all events from the History file. During this process, the display will read as
follows:
After the History file has been erased, the display will return to the History Screen.
3.6.7 Communicator
PROGRAMMING
1=HISTORY
2=COMMUNICATOR
3=ANNUNCIATORS
Programming Screen #3

Communicator Installed

The pre-installed communicator provides communication to a central station. Use of the communicator requires it be enabled in user pro-
gramming.Pressing 1 while viewing the Communicator Screen #1 will change the display to Installed No. Each press of the 1 key will
cause the display to toggle between Installed Yes and Installed No.

POTS Settings

COMMUNICATOR
1=INSTALLED
2=POTS SETTINGS
3=IP SETTINGS
Communicator Screen #1
NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018
Pressing 1 while viewing the History Screen will allow the user to select the events to be viewed as illus-
trated in the following:
1=VIEW ALL
2=VIEW ALARMS
3=VIEW OTHER EVENTS
The communicator settings allow the user to configure the settings for the pre-installed IPOTS-COM and
CELL-MOD/CELL-CAB-N if installed in the system. Pressing 2 while viewing the Programming Screen
#3 will cause the following Communicator options to be displayed:
COMMUNICATOR
1=INSTALLED
2=POTS SETTINGS
3=IP SETTINGS
Communicator Screen #1
The POTS settings configure the system when telephone lines are used to contact central station. Pressing 2
YES
while viewing the Communicator Screen #1 will display the following.
HISTORY
View Events Screen
ERASE HISTORY
PROCEED ?
1=YES
2=NO
Erase History Screen
ERASING HISTORY
PLEASE WAIT
Erase History Wait Screen
COMMUNICATOR
YES
1=PRI COMM PATH
2=SEC COMM PATH
3=TBL REPRT LIMIT 0
Communicator Screen #2
POTS SETTINGS
1=LINE 1
2=LINE 2
3=GAINS
POTS Settings Screen
Programming
COMMUNICATOR
1=REPORT SYTLE POINT
2=EVENT CODES
Communicator Screen #3