Mains And Battery Connections - Honeywell PL-1000 Installation And User Manual

Fire alarm control panel
Table of Contents

Advertisement

7.1 Mains and battery connections

Main voltage
Switch-off the 230 V AC main voltage at distribution switchboard. Before applying the mains voltage to the panel, make sure to carry out the following checks and
procedures:
Make sure that the power cable is led into the housing separately from the low voltage cables.
Prepare the power supply cable for connection as follow:
Check that the main voltage is switched off.
For safety reasons, remove the fuse from the mains supply and place in a safe place until the cable connection is complete.
Fig. 8: Mains connections
Fig. 9: Battery connection
M-169.1-SERIE-PL-EN / 09.2022
Fire Alarm Control Panel PL-1000
1. Remove the outer sheath of the cable  to provide enough slack,
approx. 80 mm, for the cables to help during connection.
2. From a loop with each conductor before presenting it on its terminal
where it is to be connected. Guide the conductor L and N  in such a
way that there is a separation from the safety ground.
3. Connect the L and N conductors directly to the terminal block  (left
and right terminal respectively). The safety ground conductor must
be connected to the panel terminal.
The terminals accept cables from 1 to 1,5 mm².
Max. 2 x 12 V DC / 7 Ah batteries can be inserted in the FACP back box. In
case of loss of the mains voltage the FACP will be powered without an
interruption by the connected battery.
The FACP can work satisfactory only on batteries, if necessary, when the
mains voltage is not available. However, this should be only for very short
periods of time, to avoid unintentional discharge of the batteries.
1. Install the batteries inside the back box on the bottom .
2. The batteries shall be positioned in such a way their terminal is close
enough to allow the connection of the short connection cable .
3. Connect the batteries using the supplied cable:
• Connect the red and black (+ / -) cable plug to the main board .
• Connect batteries with the short cable 