 Installing the heat sink outside the enclosure
When the heat sink is installed outside the enclosure, the amount of heat generated by the inverter unit is shown in the following
tables. (For details on protruding the heat sink through a panel, refer to
Voltage
200 V class
400 V class
NOTE
• The figures indicate the amount of heat generated when the output current is the rated current, power supply voltage is 220 V
(200 V class) or 440 V (400 V class), and the carrier frequency is 2 kHz.
2.3.3
From the enclosure that contains the inverter, the heat of the inverter and other equipment (transformers, lamps, resistors, etc.)
and the incoming heat such as direct sunlight must be dissipated to keep the in-enclosure temperature lower than the
permissible temperatures of the in-enclosure equipment including the inverter.
The cooling systems are classified as follows in terms of the cooling calculation method.
• Cooling by natural heat dissipation from the enclosure surface (totally enclosed type)
• Cooling by heat sink (aluminum fin, etc.)
Downloaded from
ManualsNet.com
Inverter model
Heat sink section (outside of enclosure)
FR-A820-00105(1.5K)
104
FR-A820-00167(2.2K)
161
FR-A820-00250(3.7K)
263
FR-A820-00340(5.5K)
265
FR-A820-00490(7.5K)
375
FR-A820-00630(11K)
405
FR-A820-00770(15K)
555
FR-A820-00930(18.5K)
690
FR-A820-01250(22K)
700
FR-A820-01540(30K)
1035
FR-A820-01870(37K)
1170
FR-A820-02330(45K)
1520
FR-A820-03160(55K)
1960
FR-A820-03800(75K)
2165
FR-A820-04750(90K)
2860
FR-A840-00023(0.4K)
20
FR-A840-00038(0.75K)
36
FR-A840-00052(1.5K)
42
FR-A840-00083(2.2K)
77
FR-A840-00126(3.7K)
120
FR-A840-00170(5.5K)
180
FR-A840-00250(7.5K)
260
FR-A840-00310(11K)
260
FR-A840-00380(15K)
315
FR-A840-00470(18.5K)
395
FR-A840-00620(22K)
510
FR-A840-00770(30K)
655
FR-A840-00930(37K)
780
FR-A840-01160(45K)
970
FR-A840-01800(55K)
1400
FR-A840-02160(75K)
1780
FR-A840-02600(90K)
2235
FR-A840-03250(110K)
2540
FR-A840-03610(132K)
2830
FR-A840-04320(160K)
3250
FR-A840-04810(185K)
3700
FR-A840-05470(220K)
4090
FR-A840-06100(250K)
4650
FR-A840-06830(280K)
5280

Cooling system types for inverter enclosure

search engine
page
Amount of heat generated (W)
SLD
LD
ND
95
77
147
95
240
155
235
174
340
244
365
261
500
421
615
520
665
620
925
745
1040
895
1360
1150
1740
1280
1930
1530
2530
1925
18
12
32
23
39
33
71
57
109
86
170
120
235
160
245
195
290
275
360
310
465
360
575
480
720
590
880
740
1140
890
1470
1250
1820
1540
1960
1590
2500
1950
2660
2410
3250
2690
3570
3180
4090
3570
4620
4130
44.)
Control section (inside of enclosure)
HD
SLD
LD
40
36
35
70
39
38
103
47
45
110
90
85
155
150
140
190
165
150
315
215
200
430
260
235
595
300
285
615
415
375
735
480
440
920
600
540
1000
790
710
1180
855
780
1560
1100
1000
6
35
32
12
39
38
19
43
41
38
53
49
53
55
51
90
65
60
115
85
80
145
110
100
200
135
125
265
170
160
305
230
210
385
275
250
485
330
300
610
370
340
730
600
500
925
740
630
1230
915
755
1260
1060
840
1570
1220
1100
1850
1400
1140
2380
1600
1400
2590
1760
1530
3150
2000
1760
3530
2270
1980
2. INSTALLATION AND WIRING
2.3 Installation of the inverter and enclosure design
1
2
ND
HD
33
30
35
30
3
35
32
66
50
106
75
4
109
90
169
135
200
170
260
245
5
305
265
375
315
460
380
6
550
450
650
520
775
660
28
24
7
32
28
37
31
43
37
8
44
37
50
45
60
50
85
65
9
115
85
140
120
160
145
10
210
175
250
215
280
250
400
330
540
425
660
540
710
590
850
680
1040
800
1160
1020
1370
1110
1530
1350
1770
1520