4-2. Basic System
Click [Initial Settings] in the menu bar, and then click [Basic System] to access the Basic System settings screen.
Make necessary basic system settings such as AE-200/AE-50 unit settings, network settings, and M-NET
settings, and then click [Save Settings] to send the settings to the AE-200/AE-50. A message will appear asking
whether or not to restart the AE-200/AE-50. Click [OK] to restart the AE-200/AE-50 to reflect the changes.
Note: The Basic System settings may not be accessible if logged in as a building manager.
Unit Settings
Set the AE-200/AE-50 name
and unit ID.
Network Settings
Set the AE-200/AE-50 IP
address and subnet mask.
Display Format
Set the screen display items
for the AE-200/AE-50 and
the Web browser.
Refresh
Click to import the settings
from AE-200/AE-50.
4-2-1. Unit Settings
Follow the instructions below to set the AE-200/AE-50 unit name and unit ID in the [Unit Settings] section. The
AE-200/AE-50 serial number and software version will appear.
(1) Enter the unit name in the [Name] field in 40 alphanumeric or symbol characters or less. The name entered
here will be used on the screen of the software that controls multiple AE-200/AE-50 units and will also be
used as a sender name in the error notification e-mail and e-mail alarm.
Note: The following characters cannot be used in the [Name] field: <, >, &, ", or '
(2) Enter the unit ID in the [Unit ID] field in 6 figures. Use this setting to manage the multiple unit IDs. The unit
ID entered here will be used on the screen of the software that controls multiple AE-200/AE-50 units and will
also be used as a sender ID in the error notification e-mail and e-mail alarm.
WT07138X01
13
M-NET Settings
Set the AE-200/AE-50
M-NET address and range
of prohibited controllers.
External Input Setting
Set the AE-200/AE-50
external signal input mode.
Advanced Setting
Click to display the screen
for making advanced
settings.
Save Settings
Click to save the changes
made.