Daily And Periodic Inspection - Mitsubishi Electric FR-A800 Series Instruction Manual

Hide thumbs Also See for FR-A800 Series:
Table of Contents

Advertisement

7.1.3
Area of
inspection
Surrounding
environment
Overall unit
General
Power supply
voltage
General
Conductors and
cables
Transformer/
reactor
Main circuit
Terminal block
Smoothing
aluminum
electrolytic
capacitor
Relay/contactor
Resistor
Operation
check
Control
circuit,
protection
circuit
Cooling fan
Cooling
system
Heat sink
Downloaded from
ManualsNet.com

Daily and periodic inspection

Inspection
item
Check the surrounding air temperature, humidity, dirt,
corrosive gas, oil mist, etc.
Check for unusual vibration and noise.
Check for dirt, oil, and other foreign material.
Check that the main circuit voltage and control circuit
voltage are normal.
• Check with megger (between main circuit terminals
and earth (ground) terminal).
• Check for loose screws and bolts.
• Check for overheat traces on the parts.
• Check for stains.
• Check conductors for distortion.
• Check cable sheaths for breakage and deterioration
(crack, discoloration, etc.).
Check for unusual odor and abnormal increase of
whining sound.
Check for a damage.
• Check for liquid leakage.
• Check for safety valve projection and bulge.
• Visual check and judge by the life check of the main
circuit capacitor. (Refer to
Check that the operation is normal and no chattering
sound is heard.
• Check for cracks in the resistor insulator.
• Check for a break in the cable.
• Check for an output voltage imbalance between
phases while operating the inverter alone.
• Check that no fault is found in protective and display
circuits in a sequence protective operation test.
• Check for unusual odor and discoloration.
Overall
• Check for serious rust development.
• Check for liquid leakage in a capacitor and
Aluminum
deformation trace.
electrolytic
• Visual check and judge by the life check of the control
capacitor
circuit capacitor. (Refer to
• Check for unusual vibration and noise.
• Check for loose screws and bolts.
• Check for stains.
• Check for clogging.
• Check for stains.
search engine
Description
*1
*2
page
815.)
page
815.)
7. PRECAUTIONS FOR MAINTENANCE AND INSPECTION
Inspection
Corrective action
interval
at fault
*3
occurrence
Daily Periodic
Improve the
environment.
Check fault
location and
retighten.
Clean.
Inspect the power
supply.
Contact the
manufacturer.
Retighten.
Contact the
manufacturer.
Clean.
Contact the
manufacturer.
Contact the
manufacturer.
Stop the
equipment and
contact the
manufacturer.
Stop the
equipment and
contact the
manufacturer.
Contact the
manufacturer.
Contact the
manufacturer.
Contact the
manufacturer.
Contact the
manufacturer.
Contact the
manufacturer.
Contact the
manufacturer.
Contact the
manufacturer.
Stop the
equipment and
contact the
manufacturer.
Contact the
manufacturer.
Contact the
manufacturer.
Replace the fan.
Fix with the fan
cover fixing
screws.
Clean.
Clean.
Clean.
7.1 Inspection item
1
Check by
user
2
3
4
5
6
7
8
9
10
813