5.7.2
Reset selection / disconnected PU detection / PU
stop selection
The acceptance of reset command, the inverter operation in the event of detection of the PU (operation panel / parameter unit)
disconnected, and the acceptance of stop command from the PU (PU stop function) can be selected using Pr.E100 (Reset
selection), Pr.E101 (Disconnected PU detection), and Pr.E102 (PU stop selection), respectively, or using Pr.75 alone.
Pr.
Name
Reset selection/
disconnected PU
75
detection/PU stop
selection
E100
Reset selection
Disconnected PU
E101
detection
E102
PU stop selection
E107
Reset limit
The parameters above do not return to their initial values even if Parameter clear/All parameter clear is executed.
*1
The setting range of the FR-A820-03160(55K) or lower and the FR-A840-01800(55K) or lower
*2
The setting range of the FR-A820-03800(75K) or higher and the FR-A840-02160(75K) or higher
336
5. PARAMETERS
5.7 (E) Environment setting parameters
Downloaded from
ManualsNet.com
Initial
Setting range
value
0 to 3, 14 to 17, 1000 to
1003, 1014 to 1017
0 to 3, 14 to 17, 100 to
14
103, 114 to 117, 1000 to
1003, 1014 to 1017, 1100
to 1103, 1114 to 1117
0
1
0
2
3
0
0
1
0
1
1
0
0
*2
1
search engine
*1
In the initial setting, the reset command input is always enabled,
the inverter operation continues even when PU is disconnected,
and the operation can be stopped on the PU.
*2
Reset input is always enabled.
Reset input is enabled only when the protective function is
activated.
Reset input is enabled only when the start signal is OFF.
Reset input is enabled when the protective function is activated
and the start signal is OFF.
Operation continues even when the PU is disconnected.
The inverter output is shut off when the PU is disconnected.
The inverter decelerates to a stop when the STOP key on the PU
is pressed in PU operation mode. (The PU stop function is
disabled.)
The inverter decelerates to a stop when the STOP key on the PU
is pressed in any operation mode of the PU, external, or Network.
(The PU stop function is enabled.)
Reset limit is disabled.
Reset limit is enabled.