Relationship between the analog input terminal function and the
calibration parameter
• Calibration parameter according to the terminal 1 function
Pr.868
Terminal function
setting
0 (initial
Auxiliary frequency (speed)
value)
setting
1
Magnetic flux command
Regenerative driving torque
2
limit
3
Torque command
Stall prevention operation
*1
4
level
/ torque limit / torque
command
Forward/reverse rotation speed
5
limit
6
Torque bias input
9999
No function
• Calibration parameter according to the terminal 4 function
Pr.858
Terminal function
setting
0 (initial
Frequency command
value)
1
Magnetic flux command
Stall prevention operation
4
*1
level
/ torque limit
9999
No function
*1
Use Pr.148 Stall prevention level at 0 V input or Pr.149 Stall prevention level at 10 V input to adjust bias or gain for setting the stall prevention
operation level.
Changing the frequency for the maximum analog input (Pr.125, Pr.126)
• Use Pr.125 (Pr.126) to change the frequency setting (gain) for the maximum analog input voltage (current).
(C2 (Pr.902) to C7 (Pr.905) settings do not need to be changed.)
Analog input bias/gain calibration (C2 (Pr.902) to C7 (Pr.905), C12 (Pr.917)
to C15 (Pr.918))
• The "bias" and "gain" functions serve to adjust the relationship between a setting input signal and the output frequency. A
setting input signal is such as a 0 to 5 VDC, 0 to 10 VDC, or 4 to 20 mADC signal externally input to set the output
frequency.
• Set the bias frequency of the terminal 2 input using C2 (Pr.902). (It is initially set to the frequency at 0 V.)
• Use Pr.125 to set the output frequency to the frequency command voltage (current) set by Pr.73 Analog input selection.
506
5. PARAMETERS
5.12 (T) Multi-function input terminal parameters
Downloaded from
ManualsNet.com
C2 (Pr.902) Terminal 2 frequency setting
bias frequency,
C3 (Pr.902) Terminal 2 frequency setting
bias,
C5 (Pr.904) Terminal 4 frequency setting
bias frequency,
C6 (Pr.904) Terminal 4 frequency setting
bias
C16 (Pr.919) Terminal 1 bias command
(torque/magnetic flux),
C17 (Pr.919) Terminal 1 bias (torque/
magnetic flux)
C16 (Pr.919) Terminal 1 bias command
(torque/magnetic flux),
C17 (Pr.919) Terminal 1 bias (torque/
magnetic flux)
C12 (Pr.917) Terminal 1 bias frequency
(speed),
C13 (Pr.917) Terminal 1 bias (speed)
C16 (Pr.919) Terminal 1 bias command
(torque/magnetic flux),
C17 (Pr.919) Terminal 1 bias (torque/
magnetic flux)
—
C5 (Pr.904) Terminal 4 frequency setting
bias frequency,
C6 (Pr.904) Terminal 4 frequency setting
bias
C38 (Pr.932) Terminal 4 bias command
(torque/magnetic flux),
C39 (Pr.932) Terminal 4 bias (torque/
magnetic flux)
C38 (Pr.932) Terminal 4 bias command
(torque/magnetic flux),
C39 (Pr.932) Terminal 4 bias (torque/
magnetic flux)
—
search engine
Calibration parameter
Bias setting
Pr.125 Terminal 2 frequency setting gain
frequency,
C4 (Pr.903) Terminal 2 frequency setting
gain,
Pr.126 Terminal 4 frequency setting gain
frequency,
C7 (Pr.905) Terminal 4 frequency setting
gain
C18 (Pr.920) Terminal 1 gain command
(torque/magnetic flux),
C19 (Pr.920) Terminal 1 gain (torque/
magnetic flux)
C18 (Pr.920) Terminal 1 gain command
(torque/magnetic flux),
C19 (Pr.920) Terminal 1 gain (torque/
magnetic flux)
C14 (Pr.918) Terminal 1 gain frequency
(speed),
C15 (Pr.918) Terminal 1 gain (speed)
C18 (Pr.920) Terminal 1 gain command
(torque/magnetic flux),
C19 (Pr.920) Terminal 1 gain (torque/
magnetic flux)
—
Calibration parameter
Bias setting
Pr.126 Terminal 4 frequency setting gain
frequency,
C7 (Pr.905) Terminal 4 frequency setting
gain
C40 (Pr.933) Terminal 4 gain command
(torque/magnetic flux),
C41 (Pr.933) Terminal 4 gain (torque/
magnetic flux)
C40 (Pr.933) Terminal 4 gain command
(torque/magnetic flux),
C41 (Pr.933) Terminal 4 gain (torque/
magnetic flux)
—
Gain setting
Gain setting