9.3.4

Wiring for compliance with EMC standards

• When a power supply is provided for the control circuit separately from the main circuit and a capacitive device (such as
an EMC filter or a radio noise filter) is connected, connect a noise filter (example: RTMN5006 manufactured by TDK-
Lambda Corporation) to the control circuit power supply.
MC
• Connect the inverter, noise filter, and motor to the enclosure earth (ground). (It is assumed that the enclosure earth
(ground) is connected to the ship hull earth (ground).)
• When the wiring is different from the recommended one, the noise suppression effect may be insufficient (inadequate
earthing (grounding)).
862
9. APPENDIX
9.3 Acquisition of type certification for ship classification standards (400 V class)
Downloaded from
ManualsNet.com
Capacitive
device
Noise filter
Connect two of the three phases.