5.14.17 Power failure time deceleration-to-stop function
This is a function to decelerate the motor to a stop when an instantaneous power failure or undervoltage occurs.
Pr.
261
Power failure stop
A730
selection
262
Subtracted frequency at
A731
deceleration start
263
Subtraction starting
A732
frequency
264
Power-failure
A733
deceleration time 1
265
Power-failure
A734
deceleration time 2
Power failure
266
deceleration time
A735
switchover frequency
294
UV avoidance voltage
A785
gain
668
Power failure stop
A786
frequency gain
Power failure stop
606
external signal input
T722
selection
Connection and parameter setting
Power supply
Remove the jumper
Connect terminals
R1/L11 and P/+
and terminals
S1/L21 and N/-.
• For the standard model, remove the jumpers between terminals R/L1 and R1/L11 and terminals S/L2 and S1/L21, and
connect terminals R1/L11 and P/+ and terminals S1/L21 and N/-.
• If an undervoltage, power failure or input phase loss occurs when Pr.261 Power failure stop selection ≠ "0", the motor
decelerates to a stop.
642
5. PARAMETERS
5.14 (A) Application parameters
Downloaded from
ManualsNet.com
Initial value
Name
FM
CA
0
3 Hz
60 Hz
50 Hz
5 s
9999
60 Hz
50 Hz
100%
100%
1
Inverter
R/L1
S/L2
T/L3
R1/L11
S1/L21
P/+
N/-
Standard models
search engine
Setting
range
0
Power failure time deceleration-to-stop function disabled
1, 2, 11, 12,
Power failure time deceleration-to-stop function enabled.
21, 22
Select action at an undervoltage or when a power failure occurs.
Normally, the motor runs at the initial value as it is. However,
0 to 20 Hz
adjust to suit the size of the load specification (moment of inertia,
torque).
When the output frequency ≥ the frequency set in Pr.263:
The motor decelerates if the output frequency decreases by the
0 to 590 Hz
frequency set in Pr.262.
When the output frequency < the frequency set in Pr.263:
The motor decelerates at frequencies of the output frequency.
9999
The motor decelerates from the output frequency - Pr.262.
Set the slope applicable from the deceleration start to the Pr.266
0 to 3600 s
set frequency.
Set the slope applicable for the frequency range starting at Pr.266
0 to 3600 s
and downward.
9999
Same as Pr.264.
Set the frequency at which the slope during deceleration switches
0 to 590 Hz
from the Pr.264 setting to the Pr.265 setting.
Adjust the response at undervoltage avoidance operation. Setting
0 to 200%
a large value improves the response to changes in the bus
voltage.
Adjust the response level for the operation where the deceleration
0 to 200%
time is automatically adjusted.
0
Normally open input (NO contact input specification)
1
Normally closed input (NC contact input specification)
Converter unit
R/L1
Power supply
S/L2
T/L3
Remove the jumper
R1/L11
S1/L21
Connect terminals
R1/L11 and P/+
and terminals
S1/L21 and N/-.
Description
Keep the jumpers between
terminals R1/L11 and S1/L21
connected.
Inverter
P/+
P/+
N/-
N/-
W
R1/L11
S1/L21
RDA
MRS(X10)
RSO
RES
PWF
X48
SE
SD
Separated converter type
U
V
M