Self Power Management - Mitsubishi Electric FR-A800 Series Instruction Manual

Hide thumbs Also See for FR-A800 Series:
Table of Contents

Advertisement

 Operation in combination with the self power management function for
the separated converter type
• When the self power management function is used with the separated converter type, the input signal operations are as
follows.
X95
(Converter unit
fault)
OFF
ON
OFF
*1
When Pr.138 = "0 (electronic bypass invalid at a fault)", MC2 is OFF. When Pr.138 = "1 (electronic bypass valid at a fault)", MC2 is ON.
*2
The self power management operation is followed.
*3
MC operation is as shown below.
×
Parameters referred to
Pr.11 DC injection brake operation
Pr.57 Restart coasting
Pr.58 Restart cushion
Pr.79 Operation mode
Pr.178 to Pr.189 (Input terminal function
Pr.190 to Pr.196 (Output terminal function

5.14.2 Self power management

V/F
V/F
V/F
Magnetic flux
Magnetic flux
Magnetic flux
By turning ON the magnetic contactor (MC) on the input side before the motor is started and turning OFF the MC after the motor
is stopped, power is not supplied to the main circuit, reducing the standby power.
Pr.
248
Self power management
A006
selection
137
Start waiting time
A002
254
Main circuit power OFF
A007
waiting time
30
Regenerative function
E300
selection
Downloaded from
ManualsNet.com
X96
X94
(Converter unit
(Control signal for
fault (E.OHT,
main circuit power
E.CPU))
supply MC)
ON
OFF
OFF
ON
ON
ON
ON
OFF
Notation
ON
OFF
MC2-OFF, MC3-ON during inverter operation,
MC2-ON, MC3-OFF during commercial power supply operation
timepage 715
timepage
628,
page 635
timepage 628
selectionpage 389
selection)page 521
selection)page 473
PM
PM
PM
Initial
Name
value
0
0.5 s
600 s
0
search engine
*3
MC operation
MC1
MC2
MC3
*2
×
×
×
×
×
*2
*2
*1
×
*1
×
×
MC operation
Setting
range
0
Self power management function disabled
Self power management function enabled (main circuit OFF at protective
1
function activation)
Self power management function enabled (main circuit OFF at protective
2
function activation due to a circuit failure)
Set a time period that is a little longer than the time period from the ON
0 to 100 s
signal input to the actual pick-up operation of MC1 (0.3 to 0.5 s).
Set the delay time until the main circuit power supply is turned OFF after
1 to 3600 s
the motor is stopped.
The main circuit power supply is turned OFF only when the protective
9999
function selected by Pr.248 is activated.
Power supply to the inverter: AC (terminals R, S, and T).
When power is supplied only to the control circuit, and then switched to
100, 101
be supplied to both the control and main circuits, inverter reset is not
performed.
0 to 2, 10,
11, 20, 21,
102, 110,
For other settings, refer to
111, 120,
121
Converter status
Converter fault
(E.OHT (Pr.248 = "2"))
Converter fault
(E.OHT (Pr.248 = "1"), E.CPU)
Converter normal
Converter fault
(other than the circuit failure fault or E.OHT)
(Pr.248 = "2")
Converter fault
(other than E.OHT or E.CPU)
Description
page
724.
5. PARAMETERS
5.14 (A) Application parameters
1
2
3
4
5
6
7
8
9
10
569