Storing A Device - Siemens SINAMICS MV 9LD4110-7EX70-1AA0 Operating Instructions Manual

Table of Contents

Advertisement

Preparations for use
4.6 Storage
If the drive was already connected to the cooling system and you want to store the drive again,
empty the drive completely prior to storing it. To empty the drive proceed as follows:
1. Open the connection between the cabinet piping and the external piping.
2. Drain the coolant.
3. Then tighten the screws again.
4. At one of the flanges of the cabinet piping, connect oil-free compressed air or a nitrogen
bottle. Use a suitable transition element. Blow out any residual water.
NOTICE
Damage caused by excessively high blow-out pressure
If the blow-out pressure used exceeds 6 bar, the piping and the heat sink can become damaged.
• Do not exceed the blowout pressure of 6 bar. Avoid pressure surges.
4.6.2

Storing a device

If you are not going to commission the device immediately after delivery, ensure that it is stored
correctly.
Preconditions and preparations
• Store goods only in undamaged packaging. Unpack the goods if the packaging is damaged.
Correctly store the goods corresponding to the type of goods.
• Repair any damage to the packaging before putting the equipment into storage insofar as
this is necessary to ensure proper storage conditions.