• Attach the cable shield to a shield busbar directly after the line inlet into the cabinet. Insulate
the shielded cable without any interruptions. Route the cable shield up to the device
connection.
Figure 6-1
• Bridge shield gaps (at terminals, circuit-breakers, contactors, etc.) with minimum impedance
and through the largest possible surface area.
Figure 6-2
3rd Party LCI Control Upgrade
Operating Instructions, 02/2022, A5E31872818
Shield busbar
Shielded cable
Mounting clip
Shield connection using a clip
NOTICE
Impaired functionality as a result of damaged or incorrectly connected cable shields
Incorrect connection or damaging of the cable shield can impair the function of the system.
• Handle the cable shield carefully.
• Ensure that the cable shield is correctly connected.
Shield busbars
Cables
Terminals
Bridging shield gaps
Electrical connection
6.3 Electromagnetic compatibility