Cleaning Aluminum Parts; Cleaning The Cooling Unit Filter; Repairs - Siemens SINAMICS MV 9LD4110-7EX70-1AA0 Operating Instructions Manual

Table of Contents

Advertisement

Maintenance

9.6 Repairs

9.5.2

Cleaning aluminum parts

The surface of untreated aluminum is always covered by a thin but dense oxide skin. This natural
oxide layer acts as surface protection and is the reason for the good weathering resistance of
aluminum materials. In most cases, this means that additional protective measures are
superfluous.
• Remove greasy layers using ethyl alcohol.
• If there are other very dirty areas, use ESD-compliant fiber or plastic brushes for cleaning.
9.5.3

Cleaning the cooling unit filter

You can only clean the filter in front of the intake to the converter when the cooling unit has been
switched off.
You can clean the filter at the output of the ion filter when the cooling unit is switched on. Make
sure that you close the valves to the ion exchanger.
9.6
Repairs
The following description describes repair based on a SINAMICS GL150. Carefully read and
understand the notes provided in the operating instructions of the upgraded converter.
Burns caused by inadequate cable insulation
Improperly laid or damaged cables and incorrectly attached cable shieldings can heat up in
places and cause fires or short-circuits wherever they make contact.
• Check whether all the cable shields are intact.
• Insulate damaged cable shields.
• Make sure that a short-circuit cannot occur on the power cables due to failure of the
120
NOTICE
Corrosion damage caused by unsuitable cleaning agents and cleaning instruments
Using unsuitable cleaning chemical agents and cleaning instruments may transfer metallic,
corrosion-inducing impurities onto the aluminum. This can result in corrosion damage.
• Only use cleaning agents that are suitable for aluminum.
• Use ESD-compliant brushes and cloths.
• Do not use cleaning cloths and brushes that have already been used to clean copper,
brass, bronze or other heavy metals.
• Use neither brass, bronze, or steel-wire brushes nor cloths or steel wool interwoven with
copper wire.
WARNING
insulation as a result of incorrect cable installation.
3rd Party LCI Control Upgrade
Operating Instructions, 02/2022, A5E31872818

Advertisement

Table of Contents
loading