Technical specifications and drawings
B.2 Environmental conditions
The EC declaration of conformity for the product described here, which complies with the
European Directive 2006/95/EC and corresponding standards EN 61800-5-1 and EN 60204-1,
refers only to the low-voltage section in the power unit and the control cabinet.
B.2
Environmental conditions
Climatic environmental conditions
Table B-2
Climatic environmental conditions
Ambient temperature
Relative humidity
Other climatic conditions ac‐
cording to class
Pollution degree
Mechanical ambient conditions
Table B-3
Mechanical ambient conditions
Class
144
Storage with suitable pack‐
aging
-25° C to +70° C
5% to 95%
(Only low condensation is per‐
mitted. The device must be
completely dry before com‐
missioning.)
1K22 according to DIN EN
60721‑3‑1 (IEC 60721‑3‑1)
Icing not permissible
2 without conductive pollu‐
tion according to DIN EN
50178 / VDE 0160
(IEC 62103)
Storage with suitable pack‐
aging
1M11 according to
DIN EN 60721‑3‑1
(IEC 60721‑3‑1)
Transport with suitable
packaging
-25° C to +70° C
5 % to 95 %
(Only slight condensation is
permissible. The device must
be completely dry before com‐
missioning.)
2K11 according to DIN EN
60721‑3‑2 (IEC 60721‑3‑2)
2 without conductive pollu‐
tion according to DIN EN
50178 / VDE 0160
(IEC 62103)
Transport with suitable
packaging
2M4 according to
DIN EN 60721‑3‑2
(IEC 60721‑3‑2)
Operating Instructions, 02/2022, A5E31872818
Operation (industrial)
5° C to +40° C
5% to 85%
(Condensation is not permit‐
ted)
3K22 according to DIN EN
60721‑3‑3/A2:1997
(IEC 60721‑3‑3/Ed2.2:2008)
2 without conductive pollu‐
tion according to DIN EN
50178 / VDE 0160
(IEC 62103)
Operation
3M11 according to
DIN EN 60721‑3‑3/A2:1997
(IEC 60721‑3‑3/Ed2.2:2008)
3rd Party LCI Control Upgrade