2.1 Mechanical Installation

2.1
Mechanical Installation
This section outlines specifications and the environment for proper mechanical installation of the drive.

Installation Environment

Install the drive in an environment matching the specifications below to help prolong the optimum performance life of the
drive.
Environment
Installation Area
Ambient Temperature
Humidity
Storage Temperature
Surrounding Area
Altitude
Vibration
Orientation
NOTICE: Avoid placing drive peripheral devices, transformers, or other electronics near the drive as the electrical interference created
can lead to erroneous operation. If such devices must be used in close proximity to the drive, take proper steps to shield the drive from
noise.
NOTICE: Damage to Equipment. Drive heatsink air outlet temperature may be over 80
outlet that may be damaged by 80
NOTICE: Prevent foreign matter such as metal shavings and wire clippings from falling into the drive during installation. Failure to
comply could result in damage to the drive. Place a temporary cover over the top of the drive during installation. Remove the temporary
cover before drive start-up, as the cover will reduce ventilation and cause the drive to overheat.
14
Table 2.1 Installation Environment
Indoors
-10°C to +40°C (Flange Type Enclosure)
Drive reliability improves in environments without wide temperature fluctuations.
When using the drive in an enclosure panel, install a cooling fan or air conditioner in the area to ensure that the air
temperature inside the enclosure does not exceed the specified levels.
Do not allow ice to develop on the drive.
95% RH or less and free of condensation
-20°C to +60°C
Install the drive in an area free from:
• oil mist and dust
• metal shavings, oil, water, or other foreign materials
• radioactive materials
• combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight.
Up to 1000 m without derating, up to 3000 m with output current and voltage derating.
10 Hz to 20 Hz at 9.8 m/s
2
20 Hz to 55 Hz at 5.9 m/s
(Models CIMR-A 4T0058 to 0165) or 2.0 m/s
2
Install the drive vertically to maintain maximum cooling effects.
°
C air temperature.
YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide
Conditions
(Models CIMR-A 4T0208 to 0675)
2
°
C. Do not install components above the air