YASKAWA A1000 Installation Manual page 66

Hide thumbs Also See for A1000:
Table of Contents

Advertisement

C.1 UL Standards
Terminal
Wire Gauge
Screws
M8
4/0 AWG
M10
M10
4/0 AWG × 2P
4/0 AWG × 4P
M12
M10
250 / 300 kcmil
M12
250 kcmil × 2P
M10
250 kcmil × 4P
300 kcmil × 2P
M12
300 kcmil × 4P
M10
350 kcmil
M12
M10
400 kcmil
M12
350 kcmil × 2P
M12
400 kcmil × 2P
M12
500 kcmil
M10
600 / 650 kcmil
500 kcmil × 2P
M12
600 kcmil × 2P
<1> Codes refer to a set of three crimp terminals and three insulation caps. Prepare input and output wiring using two sets for each connection.
Example 1: Models with 300 kcmil for both input and output require one set for input terminals and one set for output terminals, so the user
should order two sets of [100-051-272].
Example 2: Models with 4/0 AWG × 2P for both input and output require two sets for input terminals and two sets for output terminals, so the
user should order four sets of [100-051-560].
Note: Use crimp insulated terminals or insulated shrink tubing for wiring connections. Wires should have a continuous maximum
allowable temperature of 75°C 600 Vac UL-approved vinyl-sheathed insulation.
Low Voltage Wiring for Control Circuit Terminals
Wire low voltage wires with NEC Class 1 circuit conductors. Refer to national state or local codes for wiring. Use a UL
Listed class 2 power supply for the control circuit terminal when not using the internal control power supply of the drive.
Refer to NEC Article 725 Class 1, Class 2, and Class 3 Remote-Control, Signaling, and Power Limited Circuits for
requirements concerning class 1 circuit conductors and class 2 power supplies.
Input / Output
Open collector outputs
Digital inputs
Analog inputs / outputs
Drive Short Circuit Rating
The drive is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical Amperes, 480
Vac maximum (400 V Class) when protected by fuses listed in
66
Crimp Terminal
Model Number
Machine No.
YF-1, YET-150-1
100-8
YF-1, YET-300-1
YF-1, YET-150-1
R100-10
YF-1, YET-300-1
YF-1, YET-150-1
100-L10
YF-1, YET-300-1
YF-1, YET-150-1
100-L12
YF-1, YET-300-1
YF-1, YET-150-1
R150-10
YF-1, YET-300-1
YF-1, YET-150-1
R150-12
YF-1, YET-300-1
YF-1, YET-150-1
150-L10
YF-1, YET-300-1
YF-1, YET-150-1
150-L12
YF-1, YET-300-1
180-10
YF-1, YET-300-1
180-12
YF-1, YET-300-1
200-10
YF-1, YET-300-1
R200-12
YF-1, YET-300-1
180-L12
YF-1, YET-300-1
200-L12
YF-1, YET-300-1
325-10
YF-1, YET-300-1
325-12
YF-1, YET-300-1
Table C.3 Control Circuit Terminal Power Supply
Terminal Signal
P1, P2, PC, DM+, DM-
S1 to S8, SC, HC, H1, H2
+V, -V, A1, A2, A3, AC, AM, FM
YASKAWA ELECTRIC TOEP C710616 50B YASKAWA AC Drive - A1000 6-Phase/12-Pulse Input Installation Guide
Tool
Die Jaw
TD-228, TD-214
TD-324, TD-312
TD-228, TD-214
TD-324, TD-312
TD-228, TD-214
TD-324, TD-312
TD-228, TD-214
TD-324, TD-312
TD-229, TD-215
TD-325, TD-313
TD-229, TD-215
TD-325, TD-313
TD-229, TD-215
TD-325, TD-313
TD-229, TD-215
TD-325, TD-313
TD-326, TD-313
TD-326, TD-313
TD-327, TD-314
TD-327, TD-314
TD-326, TD-313
TD-327, TD-314
TD-328, TD-315
TD-328, TD-315
Power Supply Specifications
Requires class 2 power supply
Use the internal LVLC power supply of the
drive. Use class 2 for external power supply.
Use the internal LVLC power supply of the
drive. Use class 2 for external power supply.
Table
C.1.
Insulation
Cap
Code
<1>
Model No.
TP-100
100-068-032
TP-100
100-051-269
TP-100
100-051-559
TP-100
100-051-560
TP-150
100-051-272
TP-150
100-051-273
TP-150
100-051-561
TP-150
100-051-562
TP-200
100-066-687
TP-200
100-066-689
TP-200
100-051-563
TP-200
100-051-275
TP-200
100-066-688
TP-200
100-051-564
TP-325
100-051-565
TP-325
100-051-277

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents