Mechanical Installation - YASKAWA L1000H Quick Start Manual

Ac drive for elevator applications
Hide thumbs Also See for L1000H:
Table of Contents

Advertisement

2

Mechanical Installation

Upon Receipt
Perform the following tasks after receiving the drive:
• Inspect the drive for damage. If the drive appears damaged upon receipt, contact your supplier.
• Verify receipt of the correct model by checking the information on the nameplate. If you have received the wrong
model, contact your supplier.
Installation Environment
For optimum performance life of the drive, install the drive in an environment that meets the conditions listed below.
Environment
Installation Area
Ambient Temperature
Humidity
Storage Temperature
Surrounding Area
Altitude
Vibration
Orientation
Installation Orientation and Spacing
Always install the drive in an upright position. Leave space around
the unit for proper cooling as shown in the figure on the right.
YASKAWA Europe TOEP C710616 92D AC Drive L1000H Quick Start Guide
Indoors
IP20 enclosure: -10 to +50 °C
Drive reliability improves in environments without wide temperature fluctuations.
When using the drive in an enclosure panel, install a cooling fan or air conditioner in the area to ensure that the air
temperature inside the enclosure does not exceed the specified levels.
Do not allow ice to develop on the drive.
95% RH or less and free of condensation
-20 °C to +60 °C
Install the drive in an area free from:
• oil mist and dust
• metal shavings, oil, water or other foreign materials
• radioactive materials
• combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight
1000 m or lower, up to 3000 m with derating (for details refer to the Technical Manual)
10 to 20 Hz at 9.8 m/s
2
20 to 55 Hz at 5.9 m/s
2
Install the drive vertically to maintain maximum cooling effects.
2 Mechanical Installation
Conditions
50 mm
30 mm
30 mm
50 mm
120 mm
Air
120 mm
8