More precise information on the angle of rotation is available in Chapter "Rotating the connector
on the motor (Page 70)"
6.3.4

Connecting to a converter

6.3.4.1

Selecting and connecting cables

• Use prefabricated MOTION CONNECT cables from SIEMENS or shielded connecting cables.
The appropriate cables for your motor are listed in the Configuration Manual.
• The prefabricated MOTION CONNECT cables reduce installation costs and increase the
operational reliability
Note
The cable shielding, made up of as many strands as possible, must have a high electrical
conductivity. Braided shields made of copper or aluminum are well suited.
When connecting, comply with the following:
• Connect the shield to the converter.
• Keep the unshielded cable ends as short as possible.
• Apply the contact over a large area for a good dissipation of the high-frequency currents.
SIMOTICS S-1FK2 synchronous motors for SINAMICS S120