Connecting the converter

NOTICE
Material damage caused by an excessively high supply voltage
Material damage can occur if the supply voltage is too high for the insulation system.
• Observe the values in the following tables.
SIMOTICS machines can be operated with SINAMICS converters (uncontrolled and controlled
infeed) when maintaining the permissible voltage peaks.
The insulation system of SIMOTICS machines corresponds to the specifications laid down in
IEC 60034-18-41 according to voltage stress category C (IVIC C = high stress).
Table 6- 5
Maximum voltage peaks at the motor terminals for line (DOL) motors, converter operation possible
Rated motor voltage
V
≤ 500 V
Table 6- 6
Maximum voltage peaks at the motor terminals for motors specifically designed for converter operation
Rated motor voltage
V
≤ 500 V
> 500 V to 690 V
Depending on the step height, the voltage rise times for the individual voltage steps in the
line-to-ground voltage at the motor end of the cable must not fall below the following values.
Table 6- 7
Rise times as a function of voltage level
Step height
1MB1.33 Eagle Line shaft heights 71 ... 315
Operating Instructions, 08/2023, A5E52990459A
Û
phase-to-phase
V
pk
1500
Û
phase-to-phase
V
pk
1600
2200
V
900
1050
1260
Maximum peak voltage at the motor terminals
Û
phase-to-ground
V
pk
1100
Maximum peak voltage at the motor terminals
Û
phase-to-ground
V
pk
1400
1500
Electrical connection
6.6 Connecting the converter
DC link U
DC link U
1080
Minimum rise time t
r
ns
100
200
400
DC
V
750
DC
V
750