6.6
Connecting the converter
NOTICE
Material damage caused by an excessively high supply voltage
Material damage can occur if the supply voltage is too high for the insulation system.
• Observe the values in the following tables.
SIMOTICS machines can be operated with SINAMICS G converters and SINAMICS S
converters (uncontrolled and controlled infeed) when maintaining the permissible peak
voltages.
The insulation system of SIMOTICS machines corresponds to the specifications laid down in
IEC 60034-18-41 according to voltage stress category C (IVIC C = high stress).
Table 6- 5
Maximum voltage peaks at the motor terminals for line (DOL) motors, converter operation possible
Rated motor voltage
V
≤ 500 V
Table 6- 6
Maximum voltage peaks at the motor terminals for motors specifically designed for converter operation (e.g.
VSD 10)
Rated motor voltage
V
≤ 500 V
> 500 V to 690 V
Depending on the step height, the voltage rise times for the individual voltage steps in the
line-to-ground voltage at the motor end of the cable must not fall below the following values.
Table 6- 7
Rise times as a function of voltage level
See also
Further documents (Page 160)
1MB..1/2/3/4 - shaft heights 63 ... 355
Operating Instructions, 06/2020, A5E44455710A
Û
phase-to-phase
1500
Û
phase-to-phase
1600
2200
Step height
V
900
1050
1260
Maximum peak voltage at the motor terminals
Û
V
pk
Maximum peak voltage at the motor terminals
Û
V
pk
Electrical connection
6.6 Connecting the converter
phase-to-ground
V
pk
1100
phase-to-ground
V
pk
1400
1500
Minimum rise time t
ns
100
200
400
DC link U
DC
V
750
DC link U
DC
V
750
1080
r
85