Description; Product Overview - Emerson PACSystems RX3i User Manual

Rsti-ep dnp3 outstation module
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

User Manual
GFK-2911E
Figure 3: Application Showing Two DNP3 LANs accessing RX3i via Two EDS001
Modules
1.2

Description

The RX3i DNP3 Outstation Module, catalog number IC695EDS001 (or EDS001), hosts the
DNP3 Outstation protocol on a common RX3i ETM001 module hardware platform. Thus,
many of the specifications and behaviors are shared with the ETM001 module.
IC695EDS001 is an Ethernet-connected module which fits in the RX3i backplane and
permits the RX3i to behave as an Outstation on the DNP3 network.
The data exchanges between the EDS001 module and up to eight DNP3 Master(s) are
configurable, using a single COMMREQ instruction in the ladder logic or Structured Text
program, as detailed in Chapter 6.
1.3

Product Overview

The RX3i DNP3 Outstation Module IC695EDS001 is an Ethernet-connected module which
fits in the RX3i backplane and permits the RX3i to behave as an Outstation on the DNP3
network, where it may interact with up to eight DNP3 masters.
Module features include:
Two auto-sensing RJ-45 Ethernet ports with LED indicators
Connects via Ethernet at 10BaseT or 100BaseTX
Internal network switch with Auto-negotiate, Sense, Speed, and crossover detection
Supports Linear (daisy-chained) and Star network configurations
TCP/IP and LLA protocols supported
One Ethernet MAC Address and one IP Address per module
Time synchronization to SNTP Time Server