Optional Configuration Parameters; Parameters For Outstation Status Space (Section A); Dnp3 Polled Object Parameters - Digital Inputs & Outputs (Section B) - Emerson PACSystems RX3i User Manual

Rsti-ep dnp3 outstation module
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

User Manual
GFK-2911E
6.3

Optional Configuration Parameters

The parameters listed in the sub-sections documented in this section are optional for RX3i
DNP3 Outstation configuration files. The optional parameters are application-based, or
user-defined, configuration parameters that determine the Outstation functionality and the
responses to master station requests. All configuration parameter values should be entered
in decimal format. Refer to the parameter description to determine valid input values for
application-based, or user-defined, parameter settings.
Note:

Parameters for Outstation Status Space (Section a)

The Outstation Status Space is a 100-word data table that contains the current operational
status of the master station-Outstation connection. Set appropriate values for the
constituent parameters as required by the application. The PLC memory location assigned
to contain the Outstation Status Space is defined by the user, as follows:
Note:
For more information on Status Space 100-word data table refer to Definition of the Status
Area in Appendix A:.
Table 7:
Parameter
mComreq_Setup[10] m-type value
mComreq_Setup[11] 0
mComreq_Setup[12] address value
mComreq_Setup[13] 0
DNP3 Polled Object Parameters – Digital Inputs &
Outputs (Section b)
A digital input is defined as a DNP3 Object (Inputs) 01 Var 2 poll response. Corresponding
PLC memory type, memory address, and number of objects are required to be entered. Set
values for these parameters as required by the application.
Note:
Configuration of DNP3 outstation Parameters
Reserved parameters always have a value of zero (0).
by setting the Memory type to 0, the feature is disabled.
Value
by setting the Memory type to 0, the Object is disabled
Description
Memory Type for Outstation Status Space
Value (decimal): 8-%R, 10-%AI, 12-%AQ, 196-%W, 0-unused
Reserved
Memory Address for Outstation Status Space
Value: 1 to maximum (based on memory type)
Reserved
Chapter 6
Sep 2019
33

Advertisement

Table of Contents
loading

Table of Contents