Device Profile; Dnp V3.0 Device Profile - Emerson PACSystems RX3i User Manual

Rsti-ep dnp3 outstation module
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

User Manual
GFK-2911E
D-1

DNP V3.0 Device Profile

DNP V3.0
DEVICE PROFILE DOCUMENT
Vendor Name:
Intelligent Platforms LLC.
Device Name:
RX3i EDS001 Outstation, using the Triangle MicroWorks, Inc. DNP3 Outstation Source Code Library,
Version 3.16
Highest DNP Level Supported:
For Requests:
For Responses:
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported (the complete
list is described in the attached table):
For static (non-change-event) object requests, request qualifier codes 07 and 08 (limited quantity), and 17 and 28
(index) are supported. Static object requests sent with qualifiers 07, or 08, will be responded with qualifiers 00 or 01.
16-bit, 32-bit and Floating-Point Analog Change Events with Time may be requested.
Floating Point Analog Output Status and Output Block Objects 40 and 41 are supported.
Output Event Objects 11, 13, 42 and 43 are supported.
Maximum Data Link Frame Size (octets):
Transmitted:
Received
Maximum Data Link Re-tries:
None
Fixed 65535
Requires Data Link Layer Confirmation:
Never
Always
Sometimes
Configurable as: Never, Only for multi-frame messages, or Always

Device Profile

Device Profile
Level 3
Level 3
292
292
Device Function:
Master
Outstation
Maximum Application Fragment Size (octets):
Transmitted:
2048
Received 2048
Maximum Application Layer Re-tries:
None
Configurable
Appendix D
Sep 2019
68