Siemens SIMATIC ET 200M Operating Instructions Manual page 86

Distributed i/o device
Hide thumbs Also See for SIMATIC ET 200M:
Table of Contents

Advertisement

Connecting
5.4 Wiring the power supply and modules
3. A slotted web is arranged at the bottom side of the terminal element. Place the shield
terminal at this position onto the edge of the fixing bracket (see the figure).
4. Press the shield terminals down and swing them into the desired position.
You can attach up to four terminal elements on each of the two rows of the shield contact
element.
Figure 5-4
Attaching Cables
You can only attach one or two shielded cables per shield terminal (see figure and table
above). The cable is connected by its bare cable shield. There must be at least 20 mm of bare
cable shield. If you need more than 4 shield terminals, start wiring at the rear row of the
shield contact element.
Note
Use a sufficiently long cable between the shield terminal and the front connector. This
enables you to remove the front connector without removing the shield terminal.
86
Placing shielded 2-wire lines on the shield contact element
Fixing bracket
Shield terminals
Operating Instructions, 04/2022, EWA-4NEB7806006-09
ET 200M

Hide quick links:

Advertisement

Table of Contents
loading