Station status 2
Table 9- 5
Bit
0
1
2
3
4
5
6
7
Station status 3
Table 9- 6
Bit
0 to 6
7
9.1.3.3

Master PROFIBUS address

Definition
The PROFIBUS address of the
DP master is stored in the master PROFIBUS address diagnostic byte:
• which the DP slave has configured and
• has read and write access to the DP slave.
The master PROFIBUS address is located in byte 3 of the slave diagnosis.
FF
in byte 3
H
If the value FF
configured by the DP master.
ET 200M
Operating Instructions, 04/2022, EWA-4NEB7806006-09
Structure of station status 2 (Byte 1)
Meaning
1:
The DP slave must be reconfigured.
1:
The slave is in start-up phase.
1:
The bit in the DP slave is always "1".
1:
Response monitoring has been enabled for this DP slave.
1:
The DP slave has received the "FREEZE" control command.
1:
The DP slave has received the "SYNC" control command.
0:
The bit is always at 0.
1:
The DP slave is deactivated, that is to say, it has been removed from the current pro-
cessing.
Structure of station status 3 (Byte 2)
Meaning
0:
The bits are always at "0".
1:
There are more channel-specific diagnostic messages than can be represented in the
diagnostic frame.
in byte 3 is given as the master PROFIBUS address, the DP slave is not
H
Interrupt, error and system messages
9.1 PROFIBUS DP
191