Marine approval
Classification organizations:
• ABS (American Bureau of Shipping)
• BV (Bureau Veritas)
• DNV-GL (Det Norske Veritas)
• DNV-GL (Germanischer Lloyd)
• LRS (Lloyds Register of Shipping)
• Class NK (Nippon Kaiji Kyokai)
• CCS (China Classification Society)
• RINA (Registro Italiano Navale)
Use in industrial environments
SIMATIC products are designed for industrial applications.
Table 10- 1
Area of application
Industry
Use in residential areas
If you use the ET 200M in residential areas, you must ensure limit Class B according to
EN 55011 with regard to the emission of radio frequency interference.
Suitable measures for achieving the required limit Class B radio interference level include:
• Installation of the ET 200M in grounded control cabinets / switch boxes
• Use of noise filters in the supply cables
ET 200M
Operating Instructions, 04/2022, EWA-4NEB7806006-09
Use in industrial environments
WARNING
Personal injury and damage to property may occur.
In hazardous areas, personal injury and property damage may occur if you disconnect
plug connections while an ET 200M is in operation.
Always de-energize the ET 200M in hazardous areas before disconnecting plug
connections.
10.1 Standards and approvals
Requirement for
Interference emission
EN IEC 61000-6-4:2019
Technical Specifications
Immunity
EN IEC 61000-6-2:2019