Interrupt, error and system messages
9.1 PROFIBUS DP
Diagnostics with the IM 153-2BAx2
The IM 153-2 interface module (order number 6ES7153-2BAx2-0XB0 and higher) supplies the
same diagnostics information as the existing IM 153-2 interface module. The maximum
length of the diagnostics is now 130 bytes. Due to the 12 available slots, the IM 153-2BAx2
has a partially expanded diagnostic structure. In addition, the length of the diagnostic
interrupt has been expanded.
The following changes have been made in the diagnostics:
• The identifier-related diagnostics information comprises 3 bytes, same as previously.
Byte 8 contains an additional 4 bits for the new slots (slots 12 to 15).
• The module status is 1 byte longer and now comprises 8 bytes. Slots 12 to 15 now contain
2 new bits each.
• The diagnostic interrupt can have a maximum of 63 bytes.
Structure of the slave diagnostics with IM 153-2BAx2
Figure 9-2
188
Structure of the slave diagnostics with IM 153-2BAx2
Operating Instructions, 04/2022, EWA-4NEB7806006-09
ET 200M