MicroHarmony Cell Sizes 40 - 260A Manual
11.9 Mode 10 Data
11.9.1 Modulator to CCB
Mode 10 is dedicated to collecting diagnostic information from the CCB and is also used for issuing 'Cell Fault
Reset' commands by setting bit 2 high ('1').
0
1
2
3
4
5
6
7
11.9.2 CCB to Modulator
The response data for Mode 10 is shown below where bits 2 through 6 indicate a fault condition when set low ('0').
Table 11-10: Mode 10 Data from Power Cell to Modulator
0
1
2
3
4
5
6
7
19001467: Version 1.0
Table 11-9: Mode 10 Modulator to CCB Data
Bit
0 -> Mode definition bit
1 -> Mode definition bit 1
Cell Fault Reset
0 (not used)
0 (not used)
0 (not used)
Sync pulse for temperature engine
Odd Parity Bit
Bit
0 -> Mode definition bit 0
1 -> Mode definition bit 1
Not Q1 Out of Saturation (OOS) Fault
Not Q2 Out of Saturation (OOS) Fault
Not Q3 Out of Saturation (OOS) Fault
Not Q4 Out of Saturation (OOS) Fault
Cell Output Fuse (OK)
Odd Parity Bit
s
Communication Protocol
Description
Description
11
11-7