MicroHarmony Cell Sizes 40 - 260A Manual

11.7.2 CCB to Modulator

The CCB Mode 00 response data to the Modulator is shown below, where the Hub/Modulator boards monitor
response bit 2 to determine the operational integrity of each power cell. The CCB indicates a cell fault condition by
setting the Fault flag (bit 2) in the Mode "00" CCB response message. When this condition occurs, the outputs of all
installed cells are disabled via dedicated hardware on the Modulator.
0
1
2
3
4
5
6
7
Note: All current Harmony Drives use the Cell Bypass Enabled Indicator (bit 6) to determine proper
settings of the Voltage Regulator circuit on the Power Interface board.
19001467: Version 1.0
Table 11-6: Mode 00 Data from CCB to Modulator
Bit
0 -> Mode definition bit 0
0 -> Mode definition bit 1
Cell Fault detected by CCB
Cell DC Bus Voltage Low (Warning)
Cell Temperature Feedback (pwm at 600 Hz car-
rier)
Cell Control Input Power Valid
Cell Bypass Enabled
Odd Parity Bit
s
Communication Protocol
Description
11
11-5