Siemens SITOP UPS1600 Equipment Manual page 43

Hide thumbs Also See for SITOP UPS1600:
Table of Contents

Advertisement

Signaling
LED 5 and LED 6 (PROFINET LEDs)
Signaling
LED 5 (SF)
LEDs 5 and 6 are active only for ... -2AY0.
LED 7 (Ethernet LED /P2)
Signaling
LED 7 is active only for ... -2AY0
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
6EP4134-3AB00-...
6EP4136-3AB00-...
6EP4137-3AB00-...
Off
Module runs up, DC-UPS defective (critical hardware fault)
Green
Battery module OK
Flashing yellow
Battery outside the permitted temperature range
(1/1)
Yellow
Selected buffer time cannot be attained
Red
Battery module fault, maintenance required (incorrect polarity, battery
module not connected, high ohmic battery module connection, battery
deep discharged, fuse defective/ruptured, asymmetrical cell voltage, battery
R test unsuccessful)
LED 6 (RUN)
Off
Off
Off
Red
Flashing red
(0.1/0.1)
Flashing red
(0.5/0.5)
Flashing red
(0.5/0.5)
Flashing red
(0.5/0.5)
Off
Green
Green/yellow, alternat-
ing
Yellow
Description, device design, dimension drawing
6EP4134-3AB00-2AY0
6EP4136-3AB00-2AY0
6EP4137-3AB00-2AY0
Off
No connection to a PROFINET IO controller
Flashing green
Configuration by the PROFINET IO controller
(0.5/0.5)
Green
Application started successfully, module O.K.
Green
Application started successfully, module not O.K.
Green
Application in progress, diagnosis can be called
Flashing green
Self-test running (flashing alternately every 3 s)
(0.5/0.5)
Off
DCP device identification (LED flashes for
3 seconds)
Flashing green
Firmware update
(0.5/0.5)
6EP4134-3AB00-2AY0
6EP4136-3AB00-2AY0
6EP4137-3AB00-2AY0
Device not connected with controller
Device connected with controller, no activity
Device connected with controller, send/receive data (RX/TX)
Device connected with controller, active communication (RX/TX)
2.4 Operating displays and signaling
43