Description, device design, dimension drawing
2.1 Device description
Figure 2-3
Buffer times
NOTICE
Before the first buffer mode in the application, new battery modules must be fully charged
for 24 hours continuously without any interruption (for batteries with a capacity of 24 Ah
and above, for 48 hours).
NOTICE
Battery modules, which have been fully discharged in buffer mode, must be fully charged
again within 14 days to avoid the batteries being damaged as a result of being deeply
discharged. An unnecessary deep discharge of the battery module when buffering can be
avoided by limiting the buffer time.
Note
For the SITOP BAT1600, clearance is required above the battery module to open and close the
cover and for thermal reasons. The clearance below is required for the cable plug connector.
Additional information about the battery modules is also provided in Chapter "Correct storage
and transport (Page 232)".
24
DC power terminal
Communication terminal
Fuse
LED display (O.K.)
Reset button
Mid-point connector
Battery
Design SITOP BAT1600 38 Ah
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76