Sitop Bat1600; Standard Mounting Position - Siemens SITOP UPS1600 Equipment Manual

Hide thumbs Also See for SITOP UPS1600:
Table of Contents

Advertisement

6.2

SITOP BAT1600

6.2.1

Standard mounting position

The unit should be mounted so that the terminals are at the bottom. A clearance of at least
50 mm must be maintained above and below the device (max. cable duct depth 50 mm). No
clearance is required at the side. However, an additional clearance prevents any thermal
coupling to other sources of heat, and therefore increases the service life of the batteries (by
reducing the ambient temperature).
For 2.5 Ah, 3.2 Ah and 7.5 Ah devices
Devices 6EP4132-0JA00-0AY0 (2.5 Ah), 6EP4133-0GA00-0AY0 (3.2 Ah) and 6EP4134-0JA00-
0AY0 (7.5 Ah) can be snapped onto a TH35×15 (EN 60715) DIN rail. Batteries should always
be installed at the coolest location in the control cabinet (e.g. in the lower section of the
control cabinet). Using a wall adapter, these modules are also suitable for wall mounting
For 12 Ah device
Device 6EP4135-0GE00-0AY0 (12 Ah) is designed for being directly mounted on a wall. 4 x
M5 screws should be used for the purpose.
Note
To improve the fire protection class, for the 3.2 Ah and 12 Ah battery modules, the accessory
pack includes a transparent fire protection cover for the fuse.
For a 38 Ah device
The device 6EP4137-0GE00-0AX0 (38 Ah) is only designed for floor mounting.
Note
Install battery modules at the coolest location in the control cabinet (e.g. in the lower section
of the control cabinet).
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
Mounting position, mounting clearances
6.2 SITOP BAT1600