Engineering and remote access
3.6 Cyclic and acyclic data
0x0041: Web server parameters (reading/writing)
Data
WebserverEnabled
AutoReloadEnabled from V2.1
ReloadTime from V2.1
AutoLogout from V2.1
HttpAccessEnable from V2.1
Fill byte(s) from V2.1
124
Description
Activating/deactivating the web server of the SITOP UPS1600:
•
0: disable
•
255: enable
Enable/disable automatic update:
•
0: disable
•
255: enable
Update interval:
•
0: Off
•
5: 5s
•
10: 10s
•
20: 20s
•
30: 30s
•
60: 60s
Enable/disable automatic logoff:
•
0: disable
•
255: enable
When automatic logoff is activated, the logged on user ("Guest" or
"Admin") is automatically logged off when the SITOP UPS1600 web
server is inactive for 15 minutes.
Enable/disable HTTP access:
•
0: disable
•
255: enable
-
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
Data type
Unsigned8
Unsigned8
Unsigned8
Unsigned8
Unsigned8
Unsigned8