Mounting/removing
5.2 SITOP BAT1600
For a 38 Ah device
The device 6EP4137-0GE00-0AX0 (38 Ah) is only designed for floor mounting. The batteries
must be mounted horizontally and secured so that they cannot slide.
The fastening material is not included in the scope of delivery.
Minimum specifications for the tensioning belt: Length: 1.5 m; belt width: 25 mm; tensile
strength: 250 kg lashing force LC: 250 daN
Freestanding batteries in a control cabinet must comply with flammability Class UL94-V0.
Figure 5-8
Mounting:
1. Fasten the batteries
2. Connect the Battery Monitor to the batteries
3. Connect the mid-point connector to the batteries
4. Connect the Battery Monitor to the batteries and the mid-point connector
194
Installation 6EP4137-0GE00-0AY0 (38 Ah Pb)
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76