Siemens SITOP UPS1600 Getting Started
Hide thumbs Also See for SITOP UPS1600:

Advertisement

SITOP UPS1600 under STEP 7 V5
SITOP UPS1600 under STEP 7 V5
Getting Started
___________________
Introduction
___________________
Safety notes
___________________
Description
___________________
Assigning the IP address
___________
Installing and configuring the
SITOP UPS1600 in STEP 7
V5
___________________
Parameterizing the SITOP
UPS1600
1
2
3
4
5
6

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SITOP UPS1600

  • Page 1 ___________________ SITOP UPS1600 under STEP 7 V5 Introduction ___________________ Safety notes ___________________ Description ___________________ Assigning the IP address ___________ Installing and configuring the SITOP UPS1600 under STEP 7 V5 SITOP UPS1600 in STEP 7 ___________________ Parameterizing the SITOP UPS1600 Getting Started...
  • Page 2 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 3: Table Of Contents

    System overview ........................9 Assigning the IP address ......................11 Installing and configuring the SITOP UPS1600 in STEP 7 V5 ............17 Parameterizing the SITOP UPS1600 ..................... 21 Buffering an S7 IO controller, including the I/O when the power fails ........21 Switching off the UPS by a user program when the power fails ..........
  • Page 5: Introduction

    Operating instructions and manuals for SITOP are available in the Internet: Operating instructions/manuals (http://www.siemens.com/sitop/manuals) SITOP power supply homepage General news about our power supplies is available in the Internet at the SITOP home page (http://www.siemens.com/sitop). SITOP UPS1600 under STEP 7 V5 Getting Started,...
  • Page 6: Additional Documentation

    Introduction 1.3 Additional documentation Additional documentation Further information is available in the following documents: ● SITOP UPS1600 and SITOP UPS1100 manuals ● S7 IO controller manual ● STEP 7 V5 manual SITOP UPS1600 under STEP 7 V5 Getting Started,...
  • Page 7: Safety Notes

    EN50272-2) must be observed for the storage, assembly and operation of the lead accumulators. It must be ensured that the battery location is suitably ventilated. Potential ignition sources must be separated by at least 50 cm. SITOP UPS1600 under STEP 7 V5 Getting Started,...
  • Page 9: Description

    Application The principal tasks that you can perform with the SITOP UPS Management: ● Connecting the uninterruptible SITOP UPS1600 power supply to the IO controller S7 ● Configuring the SITOP UPS1600 uninterruptible power supply ● Protecting a computer or a computer network using the uninterruptible power supply ●...
  • Page 11: Assigning The Ip Address

    SITOP UPS1600 interface is described using the Primary Setup Tool. General information The Primary Setup Tool is a Siemens product that is free of charge and which is used to identify and configure network-conform devices. You can download the Primary Setup Tool under (http://support.automation.siemens.com/WW/View/en/19440762).
  • Page 12 1. Called the Primary Setup Tool. 2. In the Primary Setup Tool select the menu command "Settings > Set PG/PC Interface...". 3. In the dialog box "Set PG/PC Interface", select the "Access Path" tab. SITOP UPS1600 under STEP 7 V5 Getting Started,...
  • Page 13 Assigning the IP address 4. From the interfaces listed, select the Ethernet interface with which SITOP UPS1600 is connected, and confirm with "OK". SITOP UPS1600 under STEP 7 V5 Getting Started,...
  • Page 14 6. From the search results, select the SITOP UPS1600. The SITOP UPS1600 is displayed as "DC-UPS:" with its MAC address and IP address. 7. Open the menu of the SITOP UPS1600 in the tree view and select "Incl. Ethernet interface".
  • Page 15 If required, select the checkbox "Use router" and enter the IP address of the router. 10. Select the SITOP UPS1600 in the tree view. The configuration can only be loaded to the device if the SITOP UPS1600 has been selected at the upper level.
  • Page 16 11. In the Primary Setup Tool, select the menu command "Module > Download", to load the configuration to the SITOP UPS1600. You have assigned an IP address to the SITOP UPS1600, and you can now communicate with the SITOP UPS1600.
  • Page 17: Installing And Configuring The Sitop Ups1600 In Step 7 V5

    Installing and configuring the SITOP UPS1600 in STEP 7 V5 Preconditions ● STEP 7 V5 is open and a project with an S7 IO controller has been created. ● The DDF of the UPS1600 is installed correctly. ● The UPS1600 is assigned to an S7 IO controller as IO device.
  • Page 18 Installing and configuring the SITOP UPS1600 in STEP 7 V5 4. Close the "Customize" dialog box. 5. Under "PROFINET IO > I/O > UPS1600", select the version of the SITOP UPS1600 being used. SITOP UPS1600 under STEP 7 V5 Getting Started,...
  • Page 19 Installing and configuring the SITOP UPS1600 in STEP 7 V5 6. Drag and drop the UPS1600 onto the line of the subnet. The "Properties" dialog box opens. 7. Click on the "Ethernet" button. The "Properties" subdialog box opens. SITOP UPS1600 under STEP 7 V5...
  • Page 20 Installing and configuring the SITOP UPS1600 in STEP 7 V5 8. Enter an IP address for the UPS1600 at the subnet. 9. Close the two dialog boxes. The UPS1600 is connected with the subnet. 10. Save your project. You have placed the UPS1600 and integrated it into the actual project.
  • Page 21: Parameterizing The Sitop Ups1600

    Buffering an S7 IO controller, including the I/O when the power fails Preconditions ● STEP 7 V5 has been started and a project with an S7 IO controller and SITOP UPS1600 has been opened. ● The hardware has been completely wired up.
  • Page 22 1. Change into the "HW Config" window. 2. Select the UPS1600 and double-click in the configuration table on the upper entry "UPS1600 10A PN" or "UPS1600 20A PN". The configuration dialog for the UPS1600 opens. SITOP UPS1600 under STEP 7 V5 Getting Started,...
  • Page 23 Parameterizing the SITOP UPS1600 6.1 Buffering an S7 IO controller, including the I/O when the power fails 3. In the configuration dialog, go to the "Parameters" tab and open the "Buffering parameters" folder. SITOP UPS1600 under STEP 7 V5 Getting Started,...
  • Page 24 Parameterizing the SITOP UPS1600 6.1 Buffering an S7 IO controller, including the I/O when the power fails 4. Enter the buffer time in "Buffer time". SITOP UPS1600 under STEP 7 V5 Getting Started,...
  • Page 25 Parameterizing the SITOP UPS1600 6.1 Buffering an S7 IO controller, including the I/O when the power fails 5. Enter "Additional buffer time after PC shutdown". SITOP UPS1600 under STEP 7 V5 Getting Started,...
  • Page 26 6.1 Buffering an S7 IO controller, including the I/O when the power fails 6. For "Connection threshold", enter the voltage value, which, when it is fallen below the UPS, starts to buffer. SITOP UPS1600 under STEP 7 V5 Getting Started,...
  • Page 27 7. Under "Stop buffering voltage" enter the battery voltage value where buffering should be stopped for a deep discharge condition. 8. Check that "Buffering allowed" is active. If necessary, activate the "Buffering allowed" checkbox. SITOP UPS1600 under STEP 7 V5 Getting Started,...
  • Page 28 10. Confirm your entries with "OK". 11. Save your project. 12. Load the parameters into the S7 IO controller. The S7 IO controller including I/O is now buffered when the power fails. SITOP UPS1600 under STEP 7 V5 Getting Started,...
  • Page 29: Switching Off The Ups By A User Program When The Power Fails

    6.2 Switching off the UPS by a user program when the power fails Switching off the UPS by a user program when the power fails To switch off the UPS when the power fails, Siemens provides the FB160 function block in the Internet under address (http://support.automation/siemens.com/WW/view/en/78817848).
  • Page 30 Loading the block library into STEP 7 V5 1. Open the project into which the FB160 function block should be inserted. 2. Select the menu command "File > Open...". Dialog box "Open Project" is opened. SITOP UPS1600 under STEP 7 V5 Getting Started,...
  • Page 31 Parameterizing the SITOP UPS1600 6.2 Switching off the UPS by a user program when the power fails 3. Go to the "Libraries" tab and click on "Browse". The "Browse" dialog opens. SITOP UPS1600 under STEP 7 V5 Getting Started,...
  • Page 32 Parameterizing the SITOP UPS1600 6.2 Switching off the UPS by a user program when the power fails 4. Select where library "UPS1600 STEP7 V5_5" is located and confirm with "OK". The library is loaded. SITOP UPS1600 under STEP 7 V5 Getting Started,...
  • Page 33 3. Copy the four selected entries into the clipboard. 4. Open the symbol table "Symbols" in your target project. 5. Copy the four lines from the template into the table. SITOP UPS1600 under STEP 7 V5 Getting Started,...
  • Page 34 8. Select all blocks, drag them and drop them in the "Blocks" folder of your target project. The blocks are inserted into your target project. Function block FB160 has now been integrated into the project. SITOP UPS1600 under STEP 7 V5 Getting Started,...
  • Page 35 Ensure that the update cycle of the organization block being used has a direct influence on the update time of the function block. 1. In the "Blocks" folder of your project, open block "Main [OB1]" in the FBD view. SITOP UPS1600 under STEP 7 V5 Getting Started,...
  • Page 36 2. Change to the "Program elements" tab, open the folder "FB blocks", drag block "FB160" and drop it into an empty network of "Main [1]". 3. Click on the 3 question marks above function block "FB160" that has been inserted. SITOP UPS1600 under STEP 7 V5 Getting Started,...
  • Page 37 5. At block parameter "PN_ADDRESS", first enter "DW#16#" followed directly by the Profinet diagnostic address of the UPS1600 in your STEP 7 project in hexadecimal form. Example: UPS1600 diagnostic address 8183 Hexadecimal diagnostic address 1FF7 Entry at PN_address DW#16#1FF7 SITOP UPS1600 under STEP 7 V5 Getting Started,...
  • Page 38 Example: Bit memory "M0.0" or "M0.1" is set for the block parameters. Parameters Declaration Data type Description UPS_execute_reset Input Bool Shutdown signal at the UPS1600 UPS_ready_for_reset Output Bool Signal to run down the system 7. Save your project. SITOP UPS1600 under STEP 7 V5 Getting Started,...
  • Page 39 PEB 261 alarms UPS_Ready_for_buffering ready for buffering Ready for PEB 258 buffering / not ready Note You can find additional information on the I/O address area of the UPS1600 in the UPS1600 Manual. SITOP UPS1600 under STEP 7 V5 Getting Started,...
  • Page 40 – UPS_Battery_charge_level – UPS_Buffer_mode – UPS_New_alarms_pending – UPS_Ready_for_buffering 3. Save the project and load the parameters into the S7 IO controller. When the power fails, the user program now switches off the UPS. SITOP UPS1600 under STEP 7 V5 Getting Started,...

Table of Contents