Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
● Ambient temperature -25 °C ... 70 °C ● To increase the system availability, these reliable power supplies can be expanded to include SITOP supplementary modules (redundancy module, selectivity module, buffer module) as well as SITOP DC-UPS modules. SITOP PSU6200 3ph Equipment Manual, 02.2020, A5E44623402-1-76...
Page 4
24 V/10 A DC output Input 3 AC 400 - 500 V, 6EP3436-7SB00-3AX0 DC range: 450 - 600 V 24 V/20 A DC output Accessories Type Order number Reference labeling plate (160 plates) 6ES7193-6LF30-0AW0 SITOP PSU6200 3ph Equipment Manual, 02.2020, A5E44623402-1-76...
Technical data ............................35 Input ............................35 Output ............................. 37 Efficiency ..........................41 Closed-loop control ......................... 43 Protection and monitoring ....................... 44 MTBF ............................45 Mechanical system ......................... 46 Dimension drawing ......................... 47 SITOP PSU6200 3ph Equipment Manual, 02.2020, A5E44623402-1-76...
Page 6
Parallel connection to increase the power rating ..............55 Overload protection in the 24 V output circuit ................ 57 Protection against short-time voltage dips ................58 Protecting against longer power failures ................59 Environment ............................61 Service & Support ..........................63 SITOP PSU6200 3ph Equipment Manual, 02.2020, A5E44623402-1-76...
Before installation or maintenance work can begin, the system's main switch must be switched off and measures taken to prevent it being switched on again. If this instruction is not observed, touching live parts can result in death or serious injury. SITOP PSU6200 3ph Equipment Manual, 02.2020, A5E44623402-1-76...
13, 14 Do not subject the end stop to higher loads Figure 2-2 Terminal data for 6EP3433-7SB00-0AX0 and 6EP3434-7SB00-3AX0 Do not subject the end stop to higher loads Figure 2-3 Terminal data for 6EP3436-7SB00-3AX0 SITOP PSU6200 3ph Equipment Manual, 02.2020, A5E44623402-1-76...
4 %/V, or the permissible ambient temperature must be taken into account with 3 °C/V. Note It is only permissible to use an insulated screwdriver when actuating the potentiometer. For information on actuating the potentiometer (screwdriver, torque), see Connections and terminal designation (Page 10). SITOP PSU6200 3ph Equipment Manual, 02.2020, A5E44623402-1-76...
Signaling contact (13, 14) Output voltage U > 20 V closed: NOTICE: It is not permissible that the signaling contact is connected on the primary side! SITOP PSU6200 3ph Equipment Manual, 02.2020, A5E44623402-1-76...
Page 13
Output voltage U > 20 V or U > 23 V; alternative data transfer (DIP switch COM = 1) closed: NOTICE: It is not permissible that the contact is connected on the primary side! SITOP PSU6200 3ph Equipment Manual, 02.2020, A5E44623402-1-76...
Page 14
Description, device design, dimension drawing 2.4 Status displays and signaling Diagnostic monitor display Service life < 10 % SITOP PSU6200 3ph Equipment Manual, 02.2020, A5E44623402-1-76...
Switching over the output characteristic 0: Constant output voltage "standalone operation" 1: Load-dependent output voltage "parallel operation" Additional information can be found in the documents: ● Diagnostics interface (https://support.industry.siemens.com/cs/ww/en/view/109763467) ● Faceplates and communication blocks (https://support.industry.siemens.com/cs/ww/en/view/109760217) SITOP PSU6200 3ph Equipment Manual, 02.2020, A5E44623402-1-76...
(see Removal diagram (Page 21)). Then you can remove the device from the upper edge of the standard mounting rail. Figure 3-1 Mounting/removal SITOP PSU6200 3ph Equipment Manual, 02.2020, A5E44623402-1-76...
Lateral clearances do not have to be maintained. Output current as a function of the ambient temperature and mounting height Figure 4-1 6EP3433-7SB00-3AX0 output current for the standard mounting position Figure 4-2 6EP3434-7SB00-3AX0 output current for the standard mounting position SITOP PSU6200 3ph Equipment Manual, 02.2020, A5E44623402-1-76...
Page 24
Mounting position, mounting clearances 4.1 Standard mounting position Figure 4-3 6EP3436-7SB00-3AX0 output current for the standard mounting position Figure 4-4 Mounting height derating For details, see Chapter Ambient conditions (Page 53) SITOP PSU6200 3ph Equipment Manual, 02.2020, A5E44623402-1-76...
Particularly when installing on a vertically fastened standard mounting rail, additional measures may be required, e.g. to prevent the device from slipping on the standard mounting rail. 4.2.1 6EP3433-7SB00-0AX0 Figure 4-5 6EP3433-7SB00-3AX0 mounting position 1 Figure 4-6 6EP3433-7SB00-3AX0 mounting position 2 SITOP PSU6200 3ph Equipment Manual, 02.2020, A5E44623402-1-76...
Page 26
Mounting position, mounting clearances 4.2 Other mounting positions Figure 4-7 6EP3433-7SB00-3AX0 mounting position 3 Figure 4-8 6EP3433-7SB00-3AX0 mounting position 4 Figure 4-9 6EP3433-7SB00-3AX0 mounting position 5 SITOP PSU6200 3ph Equipment Manual, 02.2020, A5E44623402-1-76...
A ground-fault circuit interrupter is not permissible against indirect contact as the only protective measure. This is true for the complete line supply protected by the ground-fault circuit interrupter. SITOP PSU6200 3ph Equipment Manual, 02.2020, A5E44623402-1-76...
Page 32
6EP3433-7SB00-0AX0 International (IEC 898): (24 V/5 A) 3-pole coupled miniature circuit breaker 4 - 10 A (e.g. Siemens 5SY… - characteristic C) or circuit breaker (e.g. Siemens 3RV2…) North America (UL/CSA): 3 ph 4 - 10 A, circuit breaker (UL489-listed/Category DIVQ, e.g. Siemens 3RV27… / 3RV28…) or slow-acting fuses (acc.
In this case, ideally, the grounding at the output should be directly connected from terminal "-" of the power supply to a suitable connection point of the protective conductor system (PE) of the plant or system. SITOP PSU6200 3ph Equipment Manual, 02.2020, A5E44623402-1-76...
(25 °C), max. I²t, at 400 V AC, max. 0.15 A 0.05 A 0.1 A I²t, at 500 V AC, max. 0.25 A 0.05 A 0.1 A Integrated input fuse None None None SITOP PSU6200 3ph Equipment Manual, 02.2020, A5E44623402-1-76...
Page 36
3-pole coupled miniature 3-pole coupled miniature circuit breaker 4 - 16 A circuit breaker 4 - 10 A (e.g. Siemens 5SY… - characteristic C), or circuit breaker (e.g. Siemens 5SY… - char- (e.g. Siemens 3RV2…) acteristic C), or circuit break- North America (UL/CSA): 3 ph 4 - 16 A, circuit breaker er (e.g.
240 W 480 W Overload capability (Extra 7.5 A for 5 s/min 15 A for 5 s/min 30 A for 5 s/min Power) Can be connected in par- allel to increase the power rating SITOP PSU6200 3ph Equipment Manual, 02.2020, A5E44623402-1-76...
Page 39
When the output voltage falls below approx. 15 V, the device switches off and automatically restarts. This response is repeated as long as the overload condition is present. SITOP PSU6200 3ph Equipment Manual, 02.2020, A5E44623402-1-76...
Page 40
Technical data 6.2 Output Selector switch PO ⑪ closed (parallel operation): The output voltage falls with increasing output current. Figure 6-6 Output characteristic 6EP3434-7SB00-3AX0 parallel operation Figure 6-7 Output characteristic 6EP3436-7SB00-3AX0 parallel operation SITOP PSU6200 3ph Equipment Manual, 02.2020, A5E44623402-1-76...
400 V / 500 V AC approx. Power loss when idling 2 W / 2 W 2.9 W / 3.7 W 4.2 W / 5.6 W 400 V / 500 V AC approx. Figure 6-8 Efficiency 6EP3433-7SB00-0AX0 SITOP PSU6200 3ph Equipment Manual, 02.2020, A5E44623402-1-76...
< 10 ms 10 to 90 %, typ. Load-step settling time 1 ms 1 ms 1 ms 90 to 10 %, max. Load-step settling time < 0.5 ms 90 to 10 %, typ. SITOP PSU6200 3ph Equipment Manual, 02.2020, A5E44623402-1-76...
150 % I up to 5 s/min out rated out rated out rated Short-circuit protection Electronic trip, automatic restart (hiccup) Overload / short-circuit Diagnostics monitor, see Chapter Status displays and signal- display ing (Page 12) SITOP PSU6200 3ph Equipment Manual, 02.2020, A5E44623402-1-76...
Technical data 6.6 MTBF MTBF 6EP3433-7SB00-0AX0 (24 V/5 A) 6EP3434-7SB00-3AX0 (24 V/10 A) 6EP3436-7SB00-3AX0 (24 V/20 A) Mean Time Between Failures SN 29500: > 500000 h at 40 °C, rated load, 24 h operation SITOP PSU6200 3ph Equipment Manual, 02.2020, A5E44623402-1-76...
Type of mounting / panel mounting Type of mounting: rail mounting Type of mounting: S7-300 standard rail mounting Mounting Can be snapped onto standard TH35-15/7,5 mounting rails (EN 60715) SITOP PSU6200 3ph Equipment Manual, 02.2020, A5E44623402-1-76...
Technical data 6.8 Dimension drawing Dimension drawing See chapter Dimensions and weight (Page 18) CAD data that can be downloaded from the Internet: 6EP3433-7SB00-0AX0 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_01599) 6EP3434-7SB00-3AX0 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_01602) 6EP3436-7SB00-3AX0 (http://www.automation.siemens.com/bilddb/index.aspx?objKey=G_KT01_XX_01605) SITOP PSU6200 3ph Equipment Manual, 02.2020, A5E44623402-1-76...
EN 61558-2-16 Protection class Class I Degree of protection (EN 60529) IP20 Leakage current, typ. 1 mA Leakage current, max. 3.5 mA Test voltage see Table 7-1 Test voltage (Page 50) SITOP PSU6200 3ph Equipment Manual, 02.2020, A5E44623402-1-76...
850 V DC Production test 4200 V DC 3350 V DC 850 V DC Field test 4200 V DC 3350 V DC 850 V DC Remark: Tripping current for DC measurement: max. 10 mA SITOP PSU6200 3ph Equipment Manual, 02.2020, A5E44623402-1-76...
EN 61000-4-11 100% for 5000 ms Emitted interference EN 55022 Class B Line harmonics limitation EN 61000-3-2 Class A Generic standards EN 61000-6-2 Immunity for industrial environments EN 61000-6-3 Emission for residential areas SITOP PSU6200 3ph Equipment Manual, 02.2020, A5E44623402-1-76...
III to 2000 m (EN 50178) II from 2000 m to 6000 m (EN 50178) II to 2000 m (IEC61204-7) I from 2000 m to 6000 m (IEC61204-7) Storage: 1080 - 660 hPa (0 - 3500 m) • SITOP PSU6200 3ph Equipment Manual, 02.2020, A5E44623402-1-76...
Figure 9-1 Parallel connection Note It is not permissible to take into account simultaneous overload capability (Extra-Power 150% for 5 s/min) of several power supplies connected in parallel when configuring the power supply system. SITOP PSU6200 3ph Equipment Manual, 02.2020, A5E44623402-1-76...
Page 56
For this purpose, a suitable protective circuit (e.g. decoupling diode or DC-capable circuit breaker) must be installed between each "+" terminal of the power supply and the common connection point. SITOP PSU6200 3ph Equipment Manual, 02.2020, A5E44623402-1-76...
SIMATIC S7-1200/1500/300/400, for STEP 7 Classic and TIA Portal at no charge. You can find additional information at: Manual SITOP selectivity modules (https://support.industry.siemens.com/cs/ww/en/view/108989004) Figure 9-2 Electronic protection of 24 V loads using the SITOP PSE200U selectivity module SITOP PSU6200 3ph Equipment Manual, 02.2020, A5E44623402-1-76...
5 A. This time can be increased a multiple number of times by connecting buffer modules in parallel; the maximum buffer time is 10 s. You can find additional information at: SITOP PSE201U manual (https://support.industry.siemens.com/cs/ww/en/view/41129219) Figure 9-3 Buffering brief power failures using the SITOP PSE201U buffer module SITOP PSU6200 3ph Equipment Manual, 02.2020, A5E44623402-1-76...
Using the free-of-charge SITOP DC-UPS software tool, DC-UPS systems can be simply integrated into PC-based automation solutions. This supports further processing of the status signals and safely running down the PC. You can find additional information at: Manual, DC UPS with capacitors (https://support.industry.siemens.com/cs/ww/en/ps/18042/man) SITOP PSU6200 3ph Equipment Manual, 02.2020, A5E44623402-1-76...
Page 60
– make it easy to integrate operating and diagnostics information into STEP 7 user programs. Preconfigured UPS faceplates for WinCC visualization can be downloaded at no charge. You can find additional information at: DC UPS SITOP UPS1600/UPS1100 Manual (https://support.industry.siemens.com/cs/ww/en/view/84977415) SITOP PSU6200 3ph Equipment Manual, 02.2020, A5E44623402-1-76...
Only substances in conformance with PWIS are used (paint-wetting impairment substances) Disposal guidelines Packaging and packaging aids can and should always be recycled. The product itself may not be disposed of as domestic refuse. SITOP PSU6200 3ph Equipment Manual, 02.2020, A5E44623402-1-76...
You can access technical support through the following communication channels: ● Telephone: + 49 (0) 911 895 7222 ● Internet: Web form for support request (http://www.siemens.de/automation/support-request) Technical documentation on the Internet Operating instructions and manuals for SITOP are available in the Internet: Operating instructions/manuals (http://www.siemens.com/sitop/manuals)
Page 64
Service & Support Contact persons If you have any questions regarding the use of our products, then contact the Siemens contact person in your regional Siemens sales office. You can find these addresses as follows: ● On the Internet (http://www.automation.siemens.com/partner) ●...