2.6 Function Switch

The switch is used on setting up the baud rate between DVPCOPM-SL and CANopen network (DR0 ~ DR2). See the
table below for the baud rate and its maximum communication distance.
DR2
DR1
DR0
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
ON
ON
ON
OFF
ON
ON
ON
IN0
Note:
If the firmware of DVPCOPM-SL is under V1.32, IN0 is invalid. But the function of IN0 is as below for the firmware of
V1.32 and above.
When IN0=ON and the master and slave make the connection, the master sends the NMT message (0x82 or 0x80)
first and then the SDO message. The interval time is 100ms between the two messages. The timeout for SDO
sending is 100ms.
When IN0=OFF and the master and slave make the connection, the master sends the NMT message (0x82 or
0x80) first and then the SDO message. The interval time is 1s between the two messages. The timeout for SDO
sending is 1s.

2.7 Digital Indicator

The digital indicator provides the following two functions:
Displaying the node address of DVPCOPM-SL.
Displaying the error message of slave.
DVP-PLC Operation Manual
CANopen Communication Module DVPCOPM-SL
Baud rate (bps)
Max. communication distance (m)
10k
20k
50k
125k
250k
500k
800k
1M
See the explanation below
5,000
2,500
1,000
500
250
100
50
25
DR 2
DR 1
DR 0
I N 0