Digital Input Terminal Response Time; Setting Functions - Delta Electronics AC Drive VFD-F Series User Manual

Vfd-f series
Table of Contents

Advertisement

VFD-F Series
Setting
17
AVI(open), ACI1(close)
18
KEYPAD(open), EXT(close)
19
PID disable
20
Auxiliary 1 input
21
Auxiliary 2 input
22
Auxiliary 3 input
23
Auxiliary 4 input
24
Auxiliary 5 input
25
Auxiliary 6 input
26
Auxiliary 7 input
27
Motor No.1 output disable
28
Motor No.2 output disable
29
Motor No.3 output disable
30
Motor No.4 output disable
31
All motor outputs disable
32
Run PLC Program
33
Pause PLC Program
04 - 08

Digital Input Terminal Response Time

Settings
This parameter selects the response time of digital input terminals MI1 to MI8, EF, REV and
FWD.
AC drive will scan the digital input terminals once every 2msec. During each scan the drive
will check the status of each terminal (open or closed).
Functions
01~20
Descriptions
External selection of the Master Frequency
command. (Analog input AVI = terminal open)
or (ACI1 = terminal closed). This setting
over-rides Pr.02-00.
External selection of the Operation Command
Source. (Keypad = terminal open) or (External
terminals = terminal closed). This setting is
valid when Pr.02-01 is set to 00. Otherwise, the
Operation Command Source will follow the
setting in Pr.02-01.
Disable PID feedback control and operate via
Master Frequency Command source Pr.02-00.
Parameter value 20 to 26 program
Multi-Function Input Terminals
(Pr.04-00~Pr.04-07) to correspond with the AC
drive multi-function output terminals Pr.03-00
to 03-07 (settings 09-15).
When multiple motors are controlled by an AC
drive, these settings will allow the
corresponding motor to disable and ignore this
motor. AC drive will not accept a "Motor Output
Disabled" signal when it is running.
When multiplex motors are in circulative
control mode, this terminal can stop the motor
that power supply is not from AC drive and set
the circulative control mode disable. Now only
the motor in running keeps running.
Parameter value 32 programs Multi-Function
Input Terminal to enable the AC drive internal
PLC program. Parameter value 33 programs
an input terminal to pause the PLC program.
Note: Pr.05-00 to Pr.05-16 defines the PLC
program.
5-20