Rated Slip Frequency Of Motor; Auto Torque Compensation Gain; Torque Compensation Gain By Manual Operation - Delta Electronics AC Drive VFD-F Series User Manual

Vfd-f series
Table of Contents

Advertisement

VFD-F Series
Unsuitable setting value may cause over compensation.
07 - 05

Rated Slip Frequency of Motor

Settings
This parameter is to set rated slip of loaded motor. Users need to input rated rotation speed
according to nameplate of loaded motor. If rated frequency of motor is 60Hz, number of
motor poles is 4 and rated rotation speed of motor is 1650rpm. The rated slip frequency of
motor is 60Hz-(1650rpm X 4/120) = 5Hz.
This parameter has relation with 07-04 slip compensation. To have the best slip
compensation, this parameter must be set correctly. Incorrect setting may cause above
functions disable and even damage the motor and AC drive.
07 - 06

Auto Torque Compensation Gain

Settings
This parameter is to set auto torque compensation gain.
When motor loading is high, a part of output frequency of AC drive will be absorbed by
impedance of stator winding to make voltage of exciting inductance of motor is not enough.
Therefore, the short of gap magnet field will make a high output current but low output
torque. Auto torque compensation gain could adjust output voltage automatically according
to loading to maintain in a fixed gap magnet of the motor to get the best running situation.
If the setting of compensation gain is too great, over-exciting magnet will cause the
following situation: output current of AC drive is too great, motor is over-heating or
protection function occurs.
07 - 07

Torque Compensation Gain by Manual Operation

Settings
This parameter determines torque compensation gain by manual operation.
Torque compensation gain by manual operation won't refer to the loading situation and
adds compensation voltage on the setting V/f curve. Basically, it just changes V/f curve. It
could be reached by adjusting V/f curve.
07 - 08
Calculate Total Running Time of the Motor (Min)
Settings
07 - 09
Calculate Total Running Time of the Motor (Day)
Settings
This parameter could display running time of the motor.
0.00~20.00Hz
0.0~10.0
0.0~10.0
00 to 1439 Min
00 to 65535 Day
5-38
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
Factory Setting: 0.00
Unit: 0.01
Factory Setting: 0.0
Unit: 0.1
Factory Setting: 0.0
Unit: 1.0
Factory Setting: 00
Unit: 1
Factory Setting: 00
Unit: 1