Delta Electronics AC Drive VFD-F Series User Manual page 14

Vfd-f series
Table of Contents

Advertisement

For 230V series, 20HP and above models
460V series, 25HP and above models
NFB
R
S
T
NFB
Recommended circuit
when power supply
is turned OFF by a
fault output.
If the fault occurs, the
contact will be ON to turn
off the power and protect the power system.
Factory setting: Sink Mode
FWD/STOP
Source
REV/STOP
Sw1
E.F.
Multi-step 1
Sink
Please refer to the following
Multi-step 2
wiring for Sink mode and
Multi-step 3
Source mode.
Multi-step 4
RESET
Factory
JOG
Setting
Accel/Decel Prohibit
1/2 Accel/Decel Switch
Digital Signal Common
NO TE
Don't apply the mains voltage
directly to above terminals.
SW2
0-5V
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
+1
R(L1)
S(L2)
T(L3)
E
SA
MC
RB
RC
ON
OFF
MC
24V
FWD
REV
EF
MI1
MI2
MI3
MI4
MI5
MI6
MI7
MI8
DCM
E
+10V
Power Supply
3
0-10V
+10V 20mA
AVI
2
1
Master Frequency
0~10V (47k )
4~20mA
5k
ACI1
4~20mA
ACI2
ACM
Analog Signal Common
1:+EV
2:GND
3:SG-
4:SG+
5:NC
6:NC
Brake Unit (Optional)
VFDB
B1
P N
B2
Brake Resistor
(Optional)
-
+2
U(T1)
V(T2)
W(T3)
E
Multi-function indication
RA1
output contacts
RB1
240VAC 2.5A
120VAC 5A
RC1
28VDC 5A
Factory setting: no function
RA2
Factory setting:
RB2
no function
RC2
Multi-function Analog Output Terminals
AFM1
AFM2
Multi-
function
Input
ACM
Terminals
E
RY00
Optional
RA3
RC3
RA4
RC4
RA5
RC5
RA6
RC6
RA7
RC7
RA8
RC8
Relay B.D.
*RS-485
Main circuit (power) terminals
Serial Communication
Interface
Control circuit terminals
3-3
VFD-F Series
Motor
M
3~
Factory setting: output frequency
0~10Vdc/2mA
Factory setting: output current
0~20mA/4~20mA
Max. Impedance: 500Ω
Analog Signal Common
Shielded leads&cable
3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents