Delta Electronics AC Drive VFD-F Series User Manual page 99

Vfd-f series
Table of Contents

Advertisement

VFD-F Series
When Pr. 11-01 is set to 03 "Fixed Amount Control" and adding relay card "RY-00", VFD-F
is able to drive 1 motor under PID control mode and another 4 motors as full power running.
System powers up, VFD-F drives 1st motor as PID control mode. If VFD-F output frequency
continually surpasses 11-06 frequency setting and 11-05 time period, after time lag of
11-04, VFD-F will energize 2nd motor as full power running and 1st motor is still running
PID control mode by VFD-F.
When 1st and 2nd motors are running, if VFD-F output frequency continually surpasses
11-06 frequency setting and 11-05 time period, after time lag of 11-04, VFD-F will energize
3rd motor as full power running and 1st motor is still running PID control mode by VFD-F. At
this time, 2nd and 3rd motors are full power running.
Previous routine repeats to 3rd motor→4th motor→5th motor till VFD-F reaches proper PID
values. VFD-F only runs PID control mode to 1st motor, others run full power.
When this parameter isn't set to 00, 03-00 to 03-07 multi-function terminals will
automatically set the corresponding output motor.
VFD-F
RY00
L
N
R S T
Contactor
Contactor
Contactor
Contactor
5-66
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
M0
M1
M2
M3
M4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents