Ac Reactor; Ac Input Reactor Recommended Value; 460V Dc Choke - Delta Electronics AC Drive VFD-F Series User Manual

Vfd-f series
Table of Contents

Advertisement

VFD-F Series
B.3 AC Reactor

AC Input Reactor Recommended Value

460V, 50/60Hz, 3-Phase
KW
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
185
220

460V DC Choke

Input Voltage
NOTE
18.5kW~132kW models: built-in DC choke
160kW~220kW models: built-in AC reactor
Fundamental
HP
Amps
1
4
2
4
3
8
5
8
7.5
12
10
18
15
25
20
35
25
35
30
45
40
55
50
80
60
80
75
100
100
130
125
160
150
200
175
250
215
320
250
400
300
500
kW
0.75
1.5
2.2
3.7
5.5
7.5
11
15
Max. Continuous
Amps
6
6
12
12
18
27
37.5
52.5
52.5
67.5
82.5
120
120
150
195
240
300
375
480
560
700
HP
DC Amps
1
2
3
5
7.5
10
15
20
B-10
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
Inductance (mh)
3% impedance 5% impedance
9
6.5
5
3
2.5
1.5
1.2
0.8
0.8
0.7
0.5
0.4
0.4
0.3
0.2
0.15
0.11
0.09
0.075
0.06
0.05
Inductance (mh)
4
9
9
12
18
25
32
50
12
9
7.5
5
4.2
2.5
2
1.2
1.2
1.2
0.85
0.7
0.7
0.45
0.3
0.23
0.185
0.15
0.125
0.105
0.085
25.00
11.50
11.50
6.00
3.75
4.00
2.68
2.00