5.4 Group 3: Output Function Parameters

03 - 00
Multi-function Output terminal 1
03 - 01
Multi-function Output terminal 2
03 - 02
Multi-function Output terminal 3
03 - 03
Multi-function Output terminal 4
03 - 04
Multi-function Output terminal 5
03 - 05
Multi-function Output terminal 6
03 - 06
Multi-function Output terminal 7
03 - 07
Multi-function Output terminal 8
Settings
Setting Functions
00
No function
01
Motor No. 1
02
Motor No. 2
03
Motor No. 3
04
Motor No. 4
05
Motor No. 5
06
Motor No. 6
07
Motor No. 7
08
Motor No. 8
09
Auxiliary 1 output
10
Auxiliary 2 output
11
Auxiliary 3 output
12
Auxiliary 4 output
13
Auxiliary 5 output
14
Auxiliary 6 output
15
Auxiliary 7 output
16
Indication during operation
17
Master frequency
attained
18
Zero Speed (including shutdown)
19
Over-torque
20
External Fault
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
00-33
5-15
Descriptions
When starting circulative control, AC drive will
automatic set this parameter by 11-01 to 11-03.
Parameter value 09 to 15 program
Multi-Function Output Terminals
(Pr.03-00~Pr.03-07) to correspond with the AC
drive multi-function input terminals, Pr.04-00 to
04-07(settings 20~26).
The corresponding output will be closed during
operation (including DC brake time).
The corresponding output will be closed when
output frequency reaches master frequency
command.
The corresponding output will be closed when
the AC drive has no output voltage signal.
The corresponding output relay will be closed
when the AC drives output current exceeds the
over-torque detection level 06-04.
The corresponding output will be closed when
the EF is enabled. (Pr. 4-00 to 4-07)
VFD-F Series
Factory Setting: 00
Factory Setting: 00
Factory Setting: 00
Factory Setting: 00
Factory Setting: 00
Factory Setting: 00
Factory Setting: 00
Factory Setting: 00
5